RMC Module 92 Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`Er;h]
[ Er.h]
Compare (1 to 4)
Error Handling
Use Error Handling to
select the output value
and error output state
of this function if it
receives an error signal
from one or more sources
and it cannot determine
the output value.
[``t;g] True Good (1476)
[``t;b] True Bad (1477)
[``F;g] False Good (1478)
[``F;b] False Bad (1479)
False Bad 4022
[offset 40]
0x80 (128)
1 to 4
0xC (12)
- - - - 28012 uint
RWES
[tMr]
[`Set]
Timer Menu
[``Fn]
[ Fn]
Timer (1 to 4)
Function
Set how the timer will
function.
[`oFF] Off (62)
[`on;P] On Pulse (1471)
[`dEL] Delay (1472)
[``o;s] One Shot (1473)
[`rET] Retentive (1474)
Off 4336
[offset 50]
0x83 (131)
1 to 4
9
223 31009 uint
RWES
[SFn;A]
[SFn.A]
Timer (1 to 4)
Source Function A
Set the type of function
that will be used for this
source. This represents
the timer run signal.
[none] None (61)
[ALM] Alarm (6)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[Ent;A] Profile Event Out A
(233)
[Ent;b] Profile Event Out B
(234)
[Ent;C] Profile Event Out C
(235)
[Ent;d] Profile Event Out D
(236)
[Ent;E] Profile Event Out E
(247)
[Ent;F] Profile Event Out F
(248)
[Ent;g] Profile Event Out G
(249)
[Ent;h] Profile Event Out H
(250)
[`FUn] Function Key (1001)
[`lgC] Logic (239)
[SoF;1] Special Function Output
1 (1532)
[SoF;2] Special Function Output
2 (1533)
[SoF;3] Special Function Output
3 (1534)
[SoF;4] Special Function Output
4 (1535)
[tMr] Timer (244)
[`uAr] Variable (245)
None 4320
[offset 50]
0x83 (131)
1 to 4
1
- - - - 31001 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM