RMC Module 52 Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`Su;E]
[ Su.E]
Logic (1 to 4)
Source Value E
View the value of
Source E.
[`off] Off (62)
[``on] On (63)
- - - - 3736
[offset 80]
0x7F
(127)
1 to 4
0x1D (29)
- - - - 27029 uint
R
[`Su;F]
[ Su.F]
Logic (1 to 4)
Source Value F
View the value of
Source F.
[`off] Off (62)
[``on] On (63)
- - - - 3738
[offset 80]
0x7F
(127)
1 to 4
0x1E (30)
- - - - 27030 uint
R
[`Su;g]
[ Su.g]
Logic (1 to 4)
Value Source G
View the value of
Source G.
[`off] Off (62)
[``on] On (63)
- - - - 3740
[offset 80]
0x7F
(127)
1 to 4
0x1F (31)
- - - - 27031 uint
R
[`Su;h]
[ Su.h]
Logic (1 to 4)
Source Value H
View the value of
Source H.
[`off] Off (62)
[``on] On (63)
- - - - 3742
[offset 80]
0x7F
(127)
1 to 4
0x20 (32)
- - - - 27032 uint
R
[``o;u]
[ o.v]
Logic (1 to 4)
Output Value
View the value of this
function's output.
[`off] Off (62)
[``on] On (63)
- - - - 3746
[offset 80]
7F (127)
1 to 4
0x22 (34)
- - - - 27034 uint
R
No Dis-
play
Logic (1 to 4)
Error
Read reported cause for
logic error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
- - - - 3750
[offset 80]
0x7F
(127)
1 to 4
0x24 (36)
- - - - 27036 uint
R
[MAt]
[oPEr]
Math Menu
[`Su;A]
[ Su.A]
Math (1 to 8)
Source Value A
View the value of
Source A.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - 2870
[offset 70]
0x7D
(125)
1 to 8
0x10 (16)
- - - - 25016 float
R
[`Su;b]
[ Su.b]
Math (1 to 8)
Source Value B
View the value of
Source B.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - 2872
[offset 70]
0x7D
(125)
1 to 8
0x11 (17)
- - - - 25017 float
R
[`Su;C]
[ Su.C]
Math (1 to 8)
Source Value C
View the value of
Source C.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - 2874
[offset 70]
0x7D
(125)
1 to 8
0x12 (18)
- - - - 25018 float
R
[`Su;d]
[ Su.d]
Math (1 to 8)
Source Value D
View the value of
Source D.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - 2876
[offset 70]
0x7D
(125)
1 to 8
0x13 (19)
- - - - 25019 float
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0
and above.
R: Read
W: Write
E: EEPROM