Watlow EZ-ZONE
®
RMC Module • 142 • Chapter 5 Profiling Page
Display Step Type
Description
Parameters in Step Type
[SoAH]
[SoAk]
Step Types
Soak
A Soak Step maintains the last Target Set Points for the
designated time. The state of up to 8 event outputs may be
set or maintained.
[CM;1] Control Mode Loop 1
[CM;2] Control Mode Loop 2
[CM;3] Control Mode Loop 3
[CM;4] Control Mode Loop 4
[hoUr] Hours
[Min] Minutes
[`SEC] Seconds
[gSE1] Guaranteed Soak Enable 1
[gSE2] Guaranteed Soak Enable 2
[gSE3] Guaranteed Soak Enable 3
[gSE4] Guaranteed Soak Enable 4
[Ent1] Event 1
[Ent2] Event 2
[Ent3] Event 3
[Ent4] Event 4
[Ent5] Event 5
[Ent6] Event 6
[Ent7] Event 7
[Ent8] Event 8
[CLoc]
[CLoc]
Step Types
Wait For Time
A Wait for Time Step is available with an Access module
having the real-time calendar clock feature. This allows the
program to wait for a specified day and time before proceed-
ing to the next step. Used to have the profile execute steps
everyday or only weekdays. The state of up to 8 event out-
puts may be set or maintained.
[hoUr] Hours
[Min] Minutes
[`SEC] Seconds
[dow] Day of Week
[Ent1] Event 1
[Ent2] Event 2
[Ent3] Event 3
[Ent4] Event 4
[Ent5] Event 5
[Ent6] Event 6
[Ent7] Event 7
[Ent8] Event 8
[W;PE]
[W.PE]
Step Types
Wait For Process or Event
A Wait For Process or Event Step will wait for four process
values to match the Wait for Process Values (1 to 4), and/
or for the four Wait For Event states (1 to 4) to match the
specified state. The state of up to 8 event outputs may be
set or maintained.
[P;E1] Step Wait For Process Enable 1
[WP;1] Wait For Process 1
[P;E2] Step Wait For Process Enable 2
[WP;2] Wait For Process 2
[P;E3] Step Wait For Process Enable 3
[WP;3] Wait For Process 3
[P;E4] Step Wait For Process Enable 4
[WP;4] Wait For Process 4
[WE;1] Wait Event 1
[WE;2] Wait Event 2
[WE;3] Wait Event 3
[WE;4] Wait Event 4
[Ent1] Event 1
[Ent2] Event 2
[Ent3] Event 3
[Ent4] Event 4
[Ent5] Event 5
[Ent6] Event 6
[Ent7] Event 7
[Ent8] Event 8