Watlow EZ-ZONE
®
RMC Module • 133 • Chapter 5 Profiling Page
RMC Module • Profile Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data Type
& Read/
Write
[``SC]
[ SC]
Step (1 to 250)
Subroutine Count
If step type is Subrou-
tine, specify number
of times to execute
subroutine steps.
1 to 9,999 1 5508
[offset 100]
0x79
(121)
1 to (250)
0x23 (35)
- - - - 21035 uint
RWE
[~~JS]
[ JS]
Step (1 to 250)
Jump Step
If step type is Jump
Loop, select a step to
jump next.
Step-1 (Minimum of 1) 1 5462
[offset 100]
0x79
(121)
1 to (250)
0xC (12)
- - - - 21012 uint
RWE
[~~JC]
[ JC]
Step (1 to 250)
Jump Count
If step type is Jump
Loop, set the number
of jumps. A value of
0 creates an infinite
loop. Loops can be
nested four deep.
0 to 9,999 1 5464
[offset 100]
0x79
(121)
1 to (250)
0xD (13)
- - - - 21013 uint
RWE
[~End]
[ End]
Step (1 to 250)
End Type
If step type is End, se-
lect what the control-
ler will do when this
profile ends.
[`oFF] Control Mode set
to Off (62)
[Hold] Hold last closed-
loop set point in the pro-
file (47)*
[USEr] User, reverts to
previous set point (100)
* End Hold does not affect
the control mode, only
the closed loop set point.
The profile will return to
the control mode prior to
starting the profile.
User 5466
[offset 100]
0x79
(121)
1 to (250)
0xE (14)
- - - - 21014 uint
RWE
[Ent1]
[Ent1]
Step (1 to 250)
Event 1
Select whether output
programmed as Pro-
file Event Out A is on,
unchanged or off dur-
ing this step.
[`oFF] Off (62)
[Ucgd] Unchanged (1557)
[``on] On (63)
Un-
changed
5452
[offset 100]
0x79
(121)
1 to (250)
7
- - - - 21007 uint
RWE
[Ent2]
[Ent2]
Step (1 to 250)
Event 2
Select whether output
programmed as Pro-
file Event Out B is on,
unchanged or off dur-
ing this step.
[`oFF] Off (62)
[Ucgd] Unchanged (1557)
[``on] On (63)
Un-
changed
5454
[offset 100]
0x79
(121)
1 to (250)
8
- - - - 21008 uint
RWE
[Ent3]
[Ent3]
Step (1 to 250)
Event 3
Select whether output
programmed as Pro-
file Event Out C is on,
unchanged or off dur-
ing this step.
[`oFF] Off (62)
[Ucgd] Unchanged (1557)
[``on] On (63)
Un-
changed
5470
[offset 100]
0x79
(121)
1 to (250)
0x10 (16)
- - - - 21016 uint
RWE
Note: Some values will be rounded off to fit in the four-character display. Full values
can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set