Watlow EZ-ZONE
®
RMC Module 121 Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[SFn;D]
[SFn.D]
Profile
Source Function D
Set the type of function
that will be used for
this source. Source will
be used in profile step
type "Wait for Process or
Event" as "Event 1"
[none] None (61)
[ALM] Alarm (6)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[Ent;A] Profile Event Out A
(233)
[Ent;b] Profile Event Out B
(234)
[Ent;C] Profile Event Out C
(235)
[Ent;d] Profile Event Out D
(236)
[Ent;E] Profile Event Out E
(247)
[Ent;F] Profile Event Out F
(248)
[Ent;g] Profile Event Out G
(249)
[Ent;h] Profile Event Out H
(250)
[`FUn] Function Key (1001)
[`lgC] Logic (239)
[tMr] Timer (244)
[`uAr] Variable (245))
None 5328 0x7A
(122)
1
0x19 (25)
- - - - 22025 uint
RWE
[`si;d]
[ Si.d]
Profile
Source Instance D
Set the instance of the
function selected above.
1 to 250 1 5336 0x7A
(122)
1
0x1D (29)
- - - - 22029 uint
RWE
[`S2;D]
[ SZ.D]
Profile
Source Zone D
Set the zone of the func-
tion selected above.
0 to 16 0 5344 0x7A
(122)
1
0x21 (33)
- - - - 22033 uint
RWE
[SFn;E]
[SFn.E]
Profile
Source Function E
Set the type of function
that will be used for
this source. Source will
be used in profile step
type "Wait for Process or
Event" as "Event 1"
[nonE] None (61)
[``Ai] Analog Input (142)
[CUrr] Current (22)
[`C;Pr] Cool Power, Control
Loop (161)
[`h;Pr] Heat Power, Control
Loop (160)
[PWr] Power, Control Loop (73)
[`Lnr] Linearization (238)
[MAt] Math (240)
[``Pu] Process Value (241)
[`SP;C] Set Point Closed, Con-
trol Loop (242)
[`SP;o] Set Point Open, Control
Loop (243)
[`uAr] Variable (245)
None 5390 0x7A
(122)
1
0x38 (56)
- - - - 22056 uint
RWE
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set