Watlow EZ-ZONE
®
RMC Module • 43 • Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
No Dis-
play
Digital Input (7 to 12)
Source Error
View reported cause for
input malfunction.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
- - - - 1228
[offset 30]
0x6A
(106)
7 to C
(12)
0x0F (15)
- - - - 6015 uint
R
[`ACt]
[oPEr]
Action Menu
[`Ei;S]
[ Ei.S]
Action (1 to 8)
Event Input Status
View this input state.
[`off] Off (62)
[``on] On (63)
- - - -
1588
[offset 20]
0x6E (110)
1 to 8
5
140 10005 uint
R
[LiM]
[oPEr]
Limit Menu
[`LL;S]
[ LL.S]
Limit (1 to 4)
Low Set Point
Set the low process
value that will trigger
the limit.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
724
[offset 30]
0x70 (112)
1 to 4
3
38 12003 float
RWES
[`Lh;S]
[ Lh.S]
Limit (1 to 4)
High Set Point
Set the high process
value that will trigger
the limit.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
726
[offset 30]
0x70 (112)
1 to 4
4
39 12004 float
RWES
No Dis-
play
Limit (1-4)
Limit State
Clear limit once limit
condition is cleared.
Off (62)
None (61)
Limit High (51)
Limit Low (52)
Error (225)
- - - -
730
[offset 30]
0x70 (112)
1
6
- - - - 12006 uint
R
[`lCr]
[ LCr]
Limit (1-4)
Limit Clear Request
**
Clear limit once limit
condition is cleared.
Clear (0)
No Change (255)
- - - -
720
[offset 30]
0x70 (112)
1
1
- - - - 12001 uint
W
[`l;st]
[ L.St]
Limit (1 to 4)
Status **
Reflects whether or not
the limit is in a safe or
failed mode..
Fail (32)
Safe (1667)
- - - -
744
[offset 30]
0x70 (112)
1 to 4
0x0D (13)
- - - - 12013 uint
R
[Mon]]
[oPEr]
Monitor Menu
[C;MA]
[C.MA]
Monitor (1 to 4)
Control Mode Active
View the current con-
trol mode.
[`off] Off (62)
[AUto] Auto (10)
[MAn] Manual (54)
- - - -
2222
[offset 70]
0x97 (151)
1 to 4
2
- - - - 8002 uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0
and above.
R: Read
W: Write
E: EEPROM
S: User Set