Watlow EZ-ZONE
®
RMC Module 74 Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`L;hy]
[ L.hy]
Limit (1 to 4)
Hysteresis
Set the hysteresis for
the limit function. This
determines how far into
the safe range the pro-
cess value must move
before the limit can be
cleared.
0.001 to 9,999.000°F or units
0.001 to 5,555.000°C
3.0°F or
units
2.0°C
722
[offset 30]
0x70 (112)
1 to 4
2
41 12002 float
RWES
[SP;Lh]
[SP.Lh]
Limit (1 to 4)
Set Point High Limit
Set the high end of the
limit set point range.
-1,999.000 to 9,999.000 9,999.000 736
[offset 30]
0x70 (112)
1 to 4
9
42 12009 float
RWES
[SP;Ll]
[SP.LL]
Limit (1 to 4)
Set Point Low Limit
Set the low end of the
limit set point range.
-1,999.000 to 9,999.000 -1,999.000 738
[offset 30]
0x70 (112)
1 to 4
0xA (10)
43 12010 float
RWES
[`Lh;S]
[ Lh.S]
Limit (1 to 4)
High Set Point **
Set the high process
value that will trigger
the limit.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
726
[offset 30]
0x70 (112)
1 to 4
4
39 12004 float
RWES
[`LL;S]
[ LL.S]
Limit (1 to 4)
Low Set Point **
Set the low process
value that will trigger
the limit.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
724
[offset 30]
0x70 (112)
1 to 4
3
38 12003 float
RWES
[SFn;A]
[SFn.A]
Limit (1 to 4)
Source Function A **
Set the source for the
limit reset function.
[nonE] None (61)
[`dio] Digital I/O (1142)
[`FUn] Function Key (1001)
[`uAr] Variable (245)
None 748
[offset 30]
0x70 (112)
1 to 4
0x0F (15)
- - - - 12015 uint
RWES
[`Si;A]
[ Si.A]
Limit (1 to 4)
Source Instance A **
Set the instance of the
function selected above.
1 to 250 1 - - - - 0x70 (112)
1 to 4
0x10 (16)
- - - - 12016 uint
RWES
[`S2;a]
[ SZ.A]
Control Loop (1 to 4)
Source Zone A **
Set the zone of the func-
tion selected above.
0 to 16 0 - - - - 0x6B
(107)
1 to 4
0x11 (17)
- - - - 12017 uint
RWES
[`lCr]
[ LCr]
Limit (1 to 4)
Limit Clear Request
**
Clear limit once limit
condition is safe.
Clear (0)
No Change (255)
- - - -
720
[offset 30]
0x70 (112)
1 to 4
1
- - - - 12001 uint
W
[`l;st]
[ L.St]
Limit (1 to 4)
Status **
Reflects whether or not
the limit is in a safe or
failed mode.
Fail (32)
Safe (1667)
- - - -
744
[offset 30]
0x70 (112)
1 to 4
0x0D (13)
- - - - 12013 uint
R
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set