Seitenansicht 58
Watlow EZ-ZONE
®
RMC Module 56 Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[t;SP3]
[t.SP3]
Profile Status
*Target Set Point
Loop 3
View or change the
target set point of the
current step.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F
or
units
-18.0°C
5376 0x7A
(122)
1
0x31 (49)
- - - - 22049 float
RW
[t;SP4]
[t.SP4]
Profile Status
*Target Set Point
Loop 4
View or change the
target set point of the
current step.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F
or
units
-18.0°C
5378 0x7A
(122)
1
0x32 (50)
- - - - 22050 float
RW
[P;SP1]
[P.SP1]
Profile Status
Produced Set Point 1
Display the current set
point, even if the profile
is ramping.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - 5288 - - - - - - - - 22005 float
R
[P;SP2]
[P.SP2]
Profile Status
Produced Set Point 2
Display the current set
point, even if the profile
is ramping.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - 5380 - - - - - - - - 22051 float
R
[P;SP3]
[P.SP3]
Profile Status
Produced Set Point 3
Display the current set
point, even if the profile
is ramping.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - 5382 - - - - - - - - 22052 float
R
[P;SP4]
[P.SP4]
Profile Status
Produced Set Point 4
Display the current set
point, even if the profile
is ramping.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - 5384 - - - - - - - - 22053 float
R
No Dis-
play
Profile Status
Produced Control
Mode 1
Display the current
control mode.
Off (62)
Auto (10)
Manual (54)
- - - - 5366 0x7A
(122)
1
0x2C (44)
- - - - 22044 uint
R
No Dis-
play
Profile Status
Produced Control
Mode 2
Display the current
control mode.
Off (62)
Auto (10)
Manual (54)
- - - - 5368 0x7A
(122)
1
0x2D (45)
- - - - 22045 uint
R
No Dis-
play
Profile Status
Produced Control
Mode 3
Display the current
control mode.
Off (62)
Auto (10)
Manual (54)
- - - - 5370 0x7A
(122)
1
0x2E (46)
- - - - 22046 uint
R
No Dis-
play
Profile Status
Produced Control
Mode 4
Display the current
control mode.
Off (62)
Auto (10)
Manual (54)
- - - - 5372 0x7A
(122)
1
0x2F (47)
- - - - 22047 uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0
and above.
R: Read
W: Write
E: EEPROM
S: User Set
Seitenansicht 58