Watlow EZ-ZONE
®
RME Module 58 Chapter 4 Setup Page
RME Module Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[sas;A]
[SAS.A]
Counter (1 to 8)
State Active Source A
Set what output state will
indicate on.
[both] Both (130
[high] High (37)
[LoW] Low (53)
High 4480
[offset 40]
0x82 (130)
1 to 4
0xB (11)
- - - - 30011 uint
RWES
[sfn;B]
[SFn.b]
Counter (1 to 8)
Source Function B
Set the type of function
that will be used for this
source which is the counter
load signal.
[none] None (61)
[ALM] Alarm (6)
[`C;Pr] Cool Power, Control
Loop (161)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[Ent;A] Profile Event Out
A (233)
[Ent;b] Profile Event Out
B (234)
[Ent;C] Profile Event Out
C (235)
[Ent;d] Profile Event Out
D (236)
[Ent;E] Profile Event Out
E (247)
[Ent;F] Profile Event Out
F (248)
[Ent;g] Profile Event Out
G (249)
[Ent;h] Profile Event Out
H (250)
[`FUn] Function Key
(1001)
[`lgC] Logic (239)
[tMr] Timer (244)
[`uAr] Variable (245)
None 4462
[offset 40]
0x82 (130)
1 to 4
2
- - - - 30002 uint
RWES
[`si;B]
[ Si.b]
Counter (1 to 8)
Source Instance B
Set the instance of the
function selected above.
1 to 250 1 4466
[offset 40]
0x82 (130)
1 to 8
4
- - - - 30004 uint
RWES
[`s2;B]
[ SZ.b]
Counter (1 to 8)
Source Zone B
Set the zone of the function
selected above.
0 to 16 0 4470
[offset 40]
0x82 (130)
1 to 4
6
- - - - 30006 uint
RWES
[sas;b]
[SAS.b]
Counter (1 to 8)
State Active Source B
Set what output state will
indicate on.
[high] High (37)
[LoW] Low (53)
High 4482
[offset 40]
0x82 (130)
1 to 4
0x0C (12)
- - - - 30012 uint
RWES
[LoAd]
[LoAd]
Counter (1 to 8)
Load Value
Set the counter's initial
value.
0 to 9,999 0 4484
[offset 40]
0x82 (130)
1 to 4
0x0D (13)
215 30013 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set