Watlow EZ-ZONE RME Bedienungsanleitung Seite 40

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 124
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 39
Watlow EZ-ZONE
®
RME Module 37 Chapter 3 Operations Page
RME Module Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[``o;u]
[ o.v]
Math (1 to 8)
Output Value
View the value of this
function's output.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - 2222
[off 70]
0x7D
(125)
1 to 8
0x16 (22)
- - - - 25022 float
R
No Dis-
play
Math (1 to 8)
Error
Read reported cause for
math error.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
- - - - 2236
[offset 70]
0x7D
(125)
1 to 8
0x1D (29)
- - - - 25029 uint
R
[`SoF]
[oPEr]
Special Output Function Menu
[`Su;A]
[ Su.A]
Special Output Function
(1 to 4)
Source Value A
View the value of Source
A.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - 6632
[off 80]
0x87
(135)
1 to 4
7
- - - - 35007 float
R
[`Su;b]
[ Su.b]
Special Output Function
(1 to 4)
Source Value B
View the value of Source
B.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - 6634
[off 80]
0x87
(135)
1 to 4
8
- - - - 35008 float
R
[`o;u1]
[ o.v1]
Special Output Function
(1 to 4)
Output Value 1
View the value of this
function's Output 1.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - 6638
[off 80]
0x87
(135)
1 to 4
0xA (10)
- - - - 35010 float
R
No Dis-
play
Special Output Function
(1 to 4)
Error 1
Read reported cause for
output error.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
- - - - 6640
[offset 80]
0x87
(135)
1 to 4
0x0B (11)
- - - - 35011 uint
R
[`o;u2]
[ o.v2]
Special Output Function
(1 to 4)
Output Value 2
View the value of this
function's Output 2.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - 6642
[off 80]
0x87
(135)
1 to 4
0xC (12)
- - - - 35012 float
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EE-
PROM
S: User
Set
Seitenansicht 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 123 124

Kommentare zu diesen Handbüchern

Keine Kommentare