Watlow EZ-ZONE
®
RME Module 32 Chapter 3 Operations Page
RME Module Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter
ID
Data
Type
&
Read/
Write
[A;sir]
[A.Sir]
Alarm (1 to 4)
Alarm Silence Request
Write to this register to
silence an alarm
0 None 1466
[offset 60]
0x6D
(109)
1 to 8
0xE (14)
15 9014
uint
W
[`a;st]
[ A.St]
Alarm (1 to 8)
Alarm State
View state of alarm
Startup (88)
None (61)
Blocked (12)
Alarm low (8)
Alarm high (7)
Error (28)
None 1456
[offset 60]
0x6D
(109)
1 to 8
9
- - - - 9009
uint
R
No Dis-
play
Alarm (1 to 4)
Alarm Clearable
Read to determine if
alarm can be cleared.
[``no] No (59)
[`YES] Yes (106)
None 1462
[offset 60]
0x6D
(109)
1 to 8
0xC (12)
- - - - 9012
uint
R
No Dis-
play
Alarm (1 to 8)
Silenced
Read to see if alarm is ac-
tive but has been silenced
by Alarm Silence Request.
Yes (106)
No (59)
- - - - 1460
[offset 60]
0x6D
(109)
1 to 4
0x0B (11)
- - - - 9011 uint
R
No Dis-
play
Alarm (1 to 8)
Latched
Read to see if alarm is
currently latched.
Yes (106)
No (59)
- - - - 1458
[offset 60]
0x6D
(109)
1 to 4
0x0A (10)
- - - - 9010 uint
R
[CUrr]]
[oPEr]]
Current Menu
Note: To use the current sensing feature, Time Base (Setup
Page, Output Menu) must be set to 0.7 seconds or more.
[`C;hi]
[ C.hi]
Current (1 to 4)
High Set Point
Set the current value that
will trigger a high heater
error state.
-1,999.000 to 9,999.000 50.0 1094
[offset 50]
0x73
(115)
1 to 4
8
- - - - 15008 float
RWES
[`C;Lo]
[ C.Lo]
Current (1 to 4)
Low Set Point
Set the current value that
will trigger a low heater
error state.
-1,999.000 to 9,999.000 0.0 1096
[offset 50]
0x73
(115)
1 to 4
9
- - - - 15009 float
RWES
[`CU;r]
[ CU.r]
Sensed Current (1 to 4)
Read
View the most recent cur-
rent value monitored by
the current transformer.
-1,999.000 to 9,999.000 - - - - 1080
[offset 50]
0x73
(115)
1 to 4
1
- - - - 15001 float
R
[`C;Er]
[ C.Er]
Current (1 to 4)
Error
View the cause of the
most recent load fault.
[nonE] None (61)
[Shrt] Shorted (127)
[open] Open (65)
- - - - 1082
[offset 50]
0x73
(115)
1 to 4
2
- - - - 15002 uint
R
[`h;Er]
[ h.Er]
Current (1 to 4)
Heater Error
View the cause of the
most recent load fault
monitored by the current
transformer.
[nonE] None (61)
[high] High (37)
[Low] Low (53)
- - - - 1084
[offset 50]
0x73
(115)
1 to 4
3
- - - - 15003 uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EE-
PROM
S: User
Set