RM A M odule 33 Chapter 4 Setup Page
Access Module Setup Page
Display
Parameter name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Param-
eter
ID
Data
Type
& Read/
Write
[`Si;A]
[Si.A]
Log Point (1 to 200)
Source Instance A
Select the instance of the
source identified above..
1 to 24 1
1472
[offset 16]
0x8B
(139)
1 to C8
(200)
2
67 39002 uint
RWES
[`S2;A]
[SZ.A]
Log Point (1 to 200)
Source Zone A
Select the zone of the source
identified above.
0 to 16 0
1474
[offset 16]
0x8B
(139)
1 to C8
(200)
3
68 39003 uint
RWES
[`dEC]
[dEC]
Log Point (1 to 200)
Display Precision
Use Display Precision to set
how many decimal places to
log for the selected item.
[`Src] Source (1539)
[```0] Whole (105)
[``0;0] Tenths (94)
[`0;00] Hundredths (40)
[0;000] Thousandths (96)
Source
1482
[offset 16]
0x8B
(139)
1 to C8
(200)
7
69 39007 uint
RWES
No Dis-
play
Log Point (1 to 200)
Value
Reflects the present value of
the logged point..
-999.999 to 9,999.999 0
1476
[offset 16]
0x8B
(139)
1 to C8
(200)
4
- - - - 39004 float
R
No Dis-
play
Log Point (1 to 200)
Error
View reported cause for log
point malfunction..
None (61)
Open (65)
Shorted (127)
Measurement Error (149)
Bad Calibration Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
None
1484
[offset 16]
0x8B
(139)
1 to C8
(200)
8
- - - - 39008 uint
R
[bCUP]
[`SEt]
Backup Menu
[SAuE]
[SAuE]
Backup
Save
Set Save to Now to save
the configuration of the
other zones (modules) in the
backup memory. The setting
indicates Off when the save
action is completed. It can
take between 15 and 45 min-
utes to save the settings of
each module.
[`oFF] Off (62)
[noW] Now (1646)
Off
1270 0x8A
(138)
1
1
58 38001 uint
RW
Note: Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set