Watlow EZ-ZONE
®
RM A M odule • 27 • Chapter 4 Setup Page
Access Module • Setup Page
Display
Parameter name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Param-
eter
ID
Data
Type
& Read/
Write
[`Ad;d]
[ Ad.d]
Communications
DeviceNet™ Node Address
Set the DeviceNet™ address
for this gateway.
0 to 63
63
- - - - - - - - 83 17052 uint
RWE
[bAUd]
[bAUd]
Communications
Baud Rate DeviceNet™
Set the speed of this gate-
way's communications to
match the speed of the serial
network.
[`125] 125 kb
[`250] 250 kb
[`500] 500 kb
125
- - - - - - - - 84 17053 uint
RWE
[`FC;E]
[ FC.E]
Communications
DeviceNet™ Quick Con-
nect Enable
Allows for immediate com-
munication with the scanner
upon power up.
[``no] No (59)
[`YES} Yes (106)
No
- - - - - - - - - - - - 17054 uint
RWE
[p;add]
[P.Add]
Communications
Profibus DP Address
Set the Profibus address for
this gateway.
0 to 126
126
- - - - - - - - - - - - 17060 uint
RWE
[a;loc]
[A.Loc]
Communications
Profibus Address Lock
When set to yes the Profibus
address cannot be changed
using software. Can be
changed from the optional
RUI.
[``no] No (59)
[`yes] Yes (106)
No
- - - - - - - - - - - - 17061 uint
RWE
[stat]
[Stat]
Communications
Profibus DP Status
Current Profibus status.
[redy] Ready (1662)
[`rng] Running (149)
- - - -
- - - - - - - - - - - - 17062 uint
R
[`C_F]
[ C_F]
Communications
Display Units
Select which scale to use for
temperature passed over
communications port 2.
[```f] F (30)
[```C} C (15)
F 440
0x96
(150)
2
6
81 17050 uint
RWE
[`nU;S]
[ nU.S]
Communications
Non-volatile Save
If set to Yes all values writ-
ten to the control will be
saved in EEPROM after ap-
proximately 3 seconds.
[``no] No (59)
[`YES} Yes (106)
Yes 444 0x96 (150)
2
8
82 17051 uint
RWE
[gtW]
[`Set]
Local Remote Gateway Menu
[du;En]
[du.En]
Local Remote Gateway (1 to
17)
Device Enabled
When set to yes the gateway
attempts to establish a con-
nection with the specified
control.
[``no] No (59)
[`YES} Yes (106)
No
452
{offset 20}
0x7C
(124)
1 to 11
(17)
2
23 24002 uint
RWE
[du;St]
[du.St]
Local Remote Gateway (1 to
17)
Device Status
Indicates whether or not a
valid connection is made.
[`oFF] Off (62)
[``on} On (63)
- - - -
460
{offset 20}
0x7C
(124)
1 to 11
(17)
6
- - - - 24006 uint
R
Note: Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set