Seitenansicht 97
Watlow EZ-ZONE
®
RMS Module 95 Chapter 6 Features
Sensor Type
Process Error Enable
Calibration Offset
Units
Input Error Latching
Scale Low
Scale High
Range High
Process Error Low Value
Thermistor Curve
Resistance Range
Filter
Range Low
Clear Latch Request
TC Linearization
Analog Input
Off
Analog Input
Display Precision
Analog Input Value
Error
Process Error Enable
Calibration Offset
Units
Input Error Latching
Scale Low
Scale High
Range High
Process Error Low Value
Filter
Range Low
Clear Latch Request
TC Linearization
Analog Input
Thermocouple
Analog Input
Display Precision
Sensor Type
Sensor Type
Process Error Enable
Calibration Offset
Units
Input Error Latching
Scale Low
Scale High
Range High
Process Error Low Value
Filter
Range Low
Clear Latch Request
TC Linearization
Analog Input
Process & Potentiometer
Analog Input
Display Precision
Analog Input Value
Error
Calibration Offset
Input Error Latching
Thermistor Curve
Resistance Range
Filter
Clear Latch Request
Analog Input
Thermistor
Analog Input
Display Precision
Analog Input Value
Error
Sensor Type
Process Error Enable
Calibration Offset
Units
Input Error Latching
Scale Low
Scale High
Range High
Process Error Low Value
Filter
Range Low
Clear Latch Request
TC Linearization
Analog Input
RTD
Analog Input
Display Precision
Analog Input Value
Error
Analog Input Value
Error
Function Block Descriptions
Each of the next several pages graphically shows each of
the RMS function blocks. Note that as you view each you
will find text that is black and text that appears gray. The
gray text represents inputs that are not currently available
based on the function's defined use (red text). For instance
when the defined use of the Analog Input function is set
for RTD, TC Linearization will appear gray. Ranges speci-
fied in units or degrees F, if expressed in degrees C, range
is smaller
Analog Input Function
Note:
This Function configures and connects physical inputs to
internal functions. Control Loop primary source instance
must match Process Value or Analog Input instance.
Sensor Type
Process Error Enable
Calibration Offset
Units
Input Error Latching
Scale Low
Scale High
Range High
Process Error Low Value
Thermistor Curve
Resistance Range
Filter
Range Low
[Lin] TC Linearization : B, C, D, E, F, J, K, N, R, S, T
[Unit] Units : Absolute , Power, Process, Relative
Humidity
Temperature
[r;Lo] Range Low : -1,999.000 to 9,999.000
[r;hi] Range High : -1,999.000 to 9,999.000
[P;EE] Process Error Enable : Off, Low
[P;EL] Process Error Low Value : -100.00 to 1,000.00
[t;C] Thermistor Curve : Curve A, Curve B, Curve C, Custom
[FiL] Filter : 0.0 to 60.0 seconds
[S;Lo] Scale Low : -100.00 to 1000.00
[SEn] Sensor Type : Off, Thermocouple, Millivolts, Volts, Milliamps,
RTD 100 Ohm, RTD 1000 Ohm, 1K Potentiometer, Thermistor
(optional)
[S;hi] Scale High : -100.00 to 1000.00
Clear Latch Request
TC Linearization
Analog Input
Instances - 1 - 16 per RMS
Analog Input
Analog Input Value
Error
Display Precision
[r;r] Resistance Range : 5k, 10k, 20k, 40k
[i;CA] Calibration Offset : -1,999.000 to 9,999.000
[i;CA] Calibration Offset : -1,999.000 to 9,999.000
[i;Er] Input Error Latching : Off, On
[dEC] Display Precision : Whole, Tenths, Hundredths, Thousandths
[i;Er] Input Error : None, Open, Shorted, Measurement Error, Bad Cal
Data, Ambient Error, RTD Error, Fail, Not Sourced
[i;Er] Input Error : None, Open, Shorted, Measurement Error, Bad Cal
Data, Ambient Error, RTD Error, Fail, Not Sourced
[A in] Analog Input Value : -1,999.000 to 9,999.000
[A in] Analog Input Value : -1,999.000 to 9,999.000
[Ai]
[oPEr]
Analog Input Menu
Operation Page
[Ai]
[SEt]
Analog Input Menu
Setup Page
Overview