Watlow EZ-ZONE
®
RMS Module • 48 • Chapter 4 Setup Page
RM Scanner Module • Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[``Pu]
[`Set]
Process Value Menu
[``Fn]
[ Fn]
Process Value (1 to 16)
Function
Set the function that will
be applied to the source or
sources.
[`oFF] Off (62)
[`S;bA] Sensor Backup (1201)
[`aug] Average (1367)
[``C;o] Crossover (1368)
[`W;b] Wet Bulb / Dry Bulb
(1369)
[``s;o] Switch Over (1370)
[diFF] Differential (1373)
[rAti] Ratio (1374)
[`add] Add (1375)
[mul] Multiply (1376)
[a;dif] Absolute Difference
(1377)
[min] Minimum (1378)
[maH] Maximum (1379)
[root] Square Root (1380)
[usla] Vaisala RH Compen-
sation (1648)
[`alt] Pressure to Altitude
(1649)
Off 5220
[offset 70]
0x7E
(126)
1 to 0x10
(16)
0x15 (21)
64 26021 uint
RWES
[SFn;A]
[SFn.A]
Process Value (1 to 16)
Source Function A
Set the type of function
that will be used for this
source.
[``Ai] Analog Input (142)
[``Pu] Process Value (241)
None 5180
[offset 70]
0x7E
(126)
1 to 0x10
(16)
1
- - - - 26001 uint
RWES
[`Si;A]
[ Si.A]
Process Value (1 to 16)
Source Instance A
Set the instance of the
function selected above.
1 to 250 Based on
PV in-
stance
5190
[offset 70]
0x7E
(126)
1 to 0x10
(16)
6
- - - - 26006 uint
RWES
[SFn;b;]
[SFn.b]
Process Value (1 to 16)
Source Function B
Set the type of function
that will be used for this
source.
[nonE] None (61)
[``Ai] Analog Input (142)
[`Lnr] Linearization (238)
[MAt] Math (240)
[``Pu] Process Value (241)
[`uAr] Variable (245)
None 5182
[offset 70]
0x7D
0x7E
(126)
1 to 0x10
(16)
2
- - - - 26002 uint
RWES
[`Si;B]
[ Si.b]
Process Value (1 to 16)
Source Instance B
Set the instance of the
function selected above.
1 to 250 1 5192
[offset 70]
0x7E
(126)
1 to 0x10
(16)
7
- - - - 26007 uint
RWES
[`S2;B]
[ SZ.b]
Process Value (1 to 16)
Source Zone B
Set the zone of the function
selected above.
0 to 16 0 5202
[offset 70]
0x7E
(126)
1 to 0x10
(16)
0x0C (12))
- - - - 26012 uint
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set