Watlow EZ-ZONE RM-Scanner-Modul Bedienungsanleitung Seite 87

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 140
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 86
Watlow EZ-ZONE
®
RMS Module 84 Chapter 5 Factory Page
RM Scanner Module Factory Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[diAg]
[FCty]
Diagnostics Menu
[``Pn]
[ Pn]
Diagnostics Menu
Part Number
Display this controller's part
number.
24 - - - - 0x65
(101)
1
9
90 1009 string
R
No Dis-
play
Diagnostics Menu
Device Name
Read the device name.
EZ-ZONE RM - - - - - - - - 0x65
(101)
1
0x0B (11)
- - - - 1011 string
R
No Dis-
play
Diagnostics Menu
Device Status
Return hardware status
Fail means return to factory.
OK (138)
Fail (32)
- - - - 30 0x65
(101)
1
0x10 (16)
- - - - 1016 uint
R
[`rEu]
[ rEu]
Diagnostics Menu
Software Revision
Display this controller's firm-
ware revision number.
5 - - - - 4 0x65
(101)
1 to 5
0x11 (17)
91 1017 string
R
[S;bLd]
[S.bLd]
Diagnostics Menu
Software Build Number
Display the firmware build
number.
- - - - - - - - 8 0x65
(101)
1 to 5
5
- - - - 1005 signed
32-bit
R
[``Sn]
[ Sn]
Diagnostics Menu
Serial Number
Display the serial number.
- - - - - - - - 12 0x65
(101)
1
7
- - - - 1007 signed
32-bit
R
[dAtE]
[dAtE]
Diagnostics Menu
Date of Manufacture
Display the date code in YY-
WW format
- - - - - - - - 14 0x65
(101)
1
8
- - - - 1008 signed
32-bit
R
No Dis-
play
Diagnostics Menu
Hardware ID
Read the hardware ID.
115 115 0 0x65
(101)
1
1
- - - - 1001 signed
32-bit
R
[`CAL]
[FCty]
Calibration Menu
[`Mu]
[ Mv]
Calibration Menu (1 to 16)
Electrical Measurement
Read the raw electrical value
for this input in the units cor-
responding to the Sensor Type
(Setup Page, Analog Input
Menu) setting.
- - - - 420
[offset
90]
0x68
(104)
1 to 0x0C
(12)
0x15 (21)
- - - - 4021 float
R
[ELi;o]
[ELi.o]
Calibration Menu (1 to 16)
Electrical Input Offset
Change this value to calibrate
the low end of the input range.
-1,999.000 to 9,999.000 0.0 398
[offset
90]
0x68
(104)
1 to 0x0C
(12)
0xA (10)
- - - - 4010 float
RWES
[ELi;S]
[ELi.S]
Calibration Menu (1 to 16)
Electrical Input Slope
Adjust this value to calibrate
the slope of the input value.
-1,999.000 to 9,999.000 1.0 400
[offset
90]
0x68
(104)
1 to 0x0C
(12)
0xB (11)
- - - - 4011 float
RWES
Note: Some values will be rounded off to fit in the four-character display. Full values can
be read with another interface.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EE-
PROM
S: User
Set
Seitenansicht 86
1 2 ... 82 83 84 85 86 87 88 89 90 91 92 ... 139 140