PM Limit Controller 80 • Chapter 8 Features
**DiagnosticMenuandallassociatedpromptsarealwaysvisibleandnever writable.
Lockout Security [SLoC]&[rloC]
Factory Page Menu Parameters
Parameters
Security Level
0 1 2 3 4 5
[LoC;O]
N Y Y Y Y Y
[pas;e]
N Y Y Y Y Y
[rloC]
Y Y Y Y Y Y
[sloC]
Y Y Y Y Y Y
Note:
WhenusingMethod1Lockoutallsettingscanbemodifiedbyanyonewhoknowshowtofindtheirwayto
the [SLoC] and [rloC] parameters
Using Lockout Method 2 (Password Enable)
It is sometimes desirable to apply a higher level of security to the control where a password would be required
to access the control. If Password Enabled [pas;e] in the Factory Page under the [`loC] Menu is set to on,
an overriding Password Security will be in effect. Without the appropriate password, specified menus will re-
main inaccessible. Page and Menu access is defined in the Locked Access Level [loC;L] prompt. On the other
hand, a User with a password would have visibility restricted by the Read Lockout Security [rloC] . As an
example, with Password Enabled and the Locked Access Level [loC;L] setto1and[rloC]issetto3,the
available Pages for a User without a password would be limited to the Home and Factory Pages (locked level
1).IftheUserpasswordisenteredallpageswouldbeaccessiblewiththeexceptionoftheSetupPageasde-
finedbylevel3access.
How to Enable Password Security
Follow the steps below:
1.GototheFactoryPagebyholdingdowntheReset
RESET
key and the Advance
key for approximately six sec-
onds.
2. Push the Down¯ key one time to get to the [`loC] menu. Again push the Advance
key until the Pass-
word Enabled [pas;e] prompt is visible.
3.Pusheithertheupordownkeytoturniton.Onceon,4newpromptswillappear:
a. [loC;l] ,LockedAccessLevel(1to5)correspondingtothelockouttableabove.
b. [roll] , Rolling Password will change the Cus-tomer Code every time power is cycled.
c. [pas;u], User Password which is needed for a Us-er to acquire access to the control.
d. [pas;a], Administrator Password which is need-ed to acquire administrative access to the control.
The Administrator can either change the User and or the Administrator password or leave them in the de-
fault state. Once Password Security is enabled they will no longer be visible to anyone other than the Admin-
istrator. In other words the Lock Menu [`loC] is not available to a User. As can be seen in the formula that
follows either the User or Administrator will need to know what those passwords are to acquire a higher level
of access to the control. Back out of this menu by pushing the Infinity ˆ key. Once out of the menu, the Pass-
word Security will be enabled.
How to Acquire Access to the Control
To acquire access to any inaccessible Pages or Menus, go to the Factory Page and enter the [UloC] menu.
Once there follow the steps below:
Note:
If Password Security (Password Enabled [pas;e] is On) is enabled the two prompts mentioned below in
the first step will not be visible. If the password is unknown, call the individual or company that originally
setup the control.
1. AcquireeithertheUserPassword[pas;u] or the Administrator Password [pas;a].
2. Push the Advance
key one time where the Code [Code] prompt will be visible.