Watlow EZ-ZONE
®
PM Limit Controller • 58 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`FUn]
[`Set]
Function Key
`leu]
[ LEv]
Function Key (3 to 4)
Active Level
Selects the state in
which the Action Func-
tion will be active.
Pressing the Function
Key will toggle the se-
lected action.
high]High(37)
[Low]Low(53)
High Instance 3
Map 1 Map 2
1360 1600
Instance 4
Map 1 Map 2
1380 1620
0x6E(110)
3to4
1
137 10001 uint
RWES
[``Fn]
[ Fn]
Function Key (1 to 2)
Action Function
Program the EZ Key to
trigger an action.
Functions respond to a
level state change or
an edge level change.
Note:
The Limit Reset func-
tion is not available in
firmwarerevision11.0
and above.
[none] None
[LMr] Limit Reset, edge trig-
gered (82)
[`F;AL] Force Alarm To Occur,
leveltriggered(218)
[`AoF] Control Loops Off and
Alarms to Non-alarm State,
level triggered (220)
[`SiL] Silence Alarms, edge
triggered(108)
[ALM] Alarm Reset, edge
triggered (6)
[P;LoC] Keypad Lockout, level
triggered(217)
[usr;r] User Set Restore, edge
triggered (227)
None Instance 1
Map 1 Map 2
1364 1604
Instance 2
Map 1 Map 2
1384 1624
0x6E(110)
1to2
3
138 10003 uint
RWES
[``Fi]
[ Fi]
Function Key (1 to 2)
Function Instance
Select which instance
the EZ Key will affect.
If only one instance is
available, any selection
will affect it.
1to4 0 Instance 1
Map 1 Map 2
1364 1606
Instance 2
Map 1 Map 2
1384 1626
0x96(110)
1to2
4
139 10004 - - - -
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which scale to
use for temperature.
[```F]°F(30)
[```C]°C(15)
°F - - - - 0x67(103)
1
5
110 3005 uint
RWES
[AC;LF]
[AC.LF]
Global
AC Line Frequency
Set the frequency to the
applied ac line power
source.
[``50]50Hz(3)
[``60] 60 Hz (4)
60 Hz Instance 1
Map 1 Map 2
886 1006
0x6A(106)
1
4
89 1034 uint
RWES
[C;led]
[C.LEd]
Global
Communications LED
Action
TurnscommsLEDonor
off for selected comms
ports.
[Con1]Commport1(1189)
[Con2]Commport2(1190)
[both]Commport1and2
(13)
[`off] Off (62)
both Instance 1
Map 1 Map 2
1856 2326
0x6A(103)
1
0x0E(14)
- - - - 3014 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
* These parameters/prompts are available in this menu with firmware revisions 11.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set