Warning: Óç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or
peripheral devices. Failure to do so
may result in damage to equipment
and property, and/or injury or loss
of life.
Note:
Maximum wire size termination and
torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination or
two 1.31 mm
2
(16 AWG)
• 0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the control-
ler, do not connect wires to unused
terminals.
Note:
Maintain electrical isolation be-
tween Analog Input 1, Digital I/O,
Switched dc/open collector outputs
and Process outputs to prevent
ground loops.
Note:
The control output common
terminal and the digital common
terminal are referenced to different
voltages and must remain isolated.
Watlow EZ-ZONE
®
PM Limit Controller • 28 • Chapter 2 Install and Wire
Network Status
Indicator State Summary Requirement
Steady Off Not powered, no IP address
If the device does not have an
IP address (or is powered off),
the network status indicator
shall be steady off.
Flashing Green No connections
If the device has no estab-
lished connections, but has
obtained an IP address, the
network status indicator shall
be flashing green.
Steady Green Connected
If the device has at least one
established connection (even
to the Message Router), the
network status indicator shall
be steady green.
Flashing Red Connection timeout
If one or more of the connec-
tions in which this device is
the target has timed out, the
network status indicator shall
be flashing red. This shall be
left only if all timed out con-
nections are reestablished or
if the device is reset.
Steady Red DuplicateIP
If the device has detected
that its IP address is already
in use, the network status in-
dicator shall be steady red.
Flashing Green /
Red
Self-test
While the device is perform-
ing its power up testing, the
network status indicator shall
be flashing green / red.
Module Status
Indicator State Summary Requirement
Steady Off No power
If no power is supplied to the device, the module
status indicator shall be steady off.
Steady Green Deviceoperational
If the device is operating correctly, the module
status indicator shall be steady green.
Flashing Green Standby
If the device has not been configured, the module
status indicator shall be flashing green.
Flashing Red Minor fault
If the device has detected a recoverable minor
fault, the module status indicator shall be flash-
ing red.
NOTE: An incorrect or inconsistent configuration
would be considered a minor fault.
Steady Red Major fault
If the device has detected a non-recoverable major
fault, the module status indicator shall be steady
red.
Flashing Green / Red Self-test
While the device is performing its power up test-
ing, the module status indicator shall be flashing
green / red.
Link Status
Indicator State Summary Requirement
Steady Off
Not powered,
unknown link speed
If the device cannot determine link speed
or power is off, the network status indicator
shall be steady off.
Green - - - -
If cable is wired and connected correctly, the
LEDwillbeGreen.