CPC400 Series User’s Guide Chapter 2: Installation
Doc. 0600-2900-2000 Watlow Anafaze 25
CAUTION!
Without proper grounding, the CPC400 may not
operate properly or may be damaged.
CAUTION!
To prevent damage from incorrect connections,
do not turn on the ac power before testing the
connections as explained in Testing the System
on page 26.
NOTE!
Do not connect the controller’s dc common
(COM) to earth ground . Doing so will defeat the
noise protection circuitry, making measurements
less stable.
Figure 2.13 Power Connections with the
CPC400 Power Supply
** Connect terminals to ac panel ground.
solid-state relay
G
N
D
Add jumper *
C
O
M
+
5
Serial DAC
CPC400
Power Supply
1 2 3 4
white
black
green
G
H
N
120/240
Supply
**
**
* If using 5VÎ (dc) for outputs, jumper 5V common to 15V common.
C
O
M
V
+
VÅ (ac)
+V1 (5V)
0 (5V COM)
+V2 (+15V)
COM (15V COM)
-V2 (-15V)
ACL (AC Line)
ACN (AC Neutral)
(Ground)
solid-state relay
solid-state relay
solid-state relay