
CPC400 Series User’s Guide Chapter 5: Menu and Parameter Reference
Doc. 0600-2900-2000 Watlow Anafaze 133
Values: Unacknowledged (1) or acknowledged (0)
Modbus Address (Loops 1 to 9): 40511 to 40519
Parameter Number: 30
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 30.1 to 30.9
Alarm Enable
Enable or disable an alarm. Table 5.18 shows the bit to set
or read for each alarm. This parameter is available only for
serial communications and LogicPro programs. See Bit-
Wise Values on page 78 for information on reading or set-
ting this parameter.
Values: Disabled (0) or enabled (1)
Default: Disabled (0)
Modbus Address (Loops 1 to 9): 40528 to 40536
Parameter Number: 31
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 31.1 to 31.9
Table 5.18 Bit Positions for Alarm Enable and
Alarm Function
Alarm Function
Choose whether an alarm behaves as a standard alarm or
as a boost output. For descriptions of the standard and
boost functions, see Table 5.16 on page 122. Table 5.18
shows the bit to set or read for each alarm. See Bit-Wise
Values on page 78 for information on reading or setting this
parameter.
This parameter is available only for serial communications
and LogicPro programs.
Values: Standard alarm (0) or boost output (1)
Default: Standard alarm (0)
Modbus Address (Loops 1 to 9): 40494 to 40502
Parameter Number: 29
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 29.1 to 29.9
Alarm Bit
Low Deviation Alarm Third
High Deviation Alarm Fourth
Alarm Low Fifth
Alarm High Sixth
Kommentare zu diesen Handbüchern