Setup
CLS User’s Guide 75
Display Format
This menu appears under the Set up Loop Inputs main menu. It lets you
select a display format for a linear input. Choose a format appropriate
for your input range and accuracy. (You will only see the Display
Format menu if you are editing a linear input.)
Selectable values:
The CLS has several available display formats, as
shown below. This table also shows the high and low PV values.
High Process Value
This menu appears under the Set up Loop Inputs main menu. Use it to
enter a high process value. The high process value and the high reading
value together define one of the points on the linear scaling function's
conversion line.
Selectable values:
See table on the previous page.
Display Format Default High PV Default Low PV
-9999 to +30000 10000 0
-999 to +3000 1000 0
-999.9 to +3000.0 1000.0 .0
-99.99 to +300.00 100.00 .00
-9.999 to +30.000 10.000 .000
-.9999 to +3.0000 1.0000 .0000
ALARM SETPOINT STATUS OUT%
04 DISP FORMAT ?
-999 to 3000
ALARM SETPOINT STATUS OUT%
01 INPUT SCALING
HI PV ? 1000
º
F
Kommentare zu diesen Handbüchern