128 CLS Users Guide
Appendix A: Ramp Soak
Setting Segment Tolerance
Use this menu to set a positive or negative tolerance value for each
segment. this value is displayed in the engineering units of the process
and is a deviation from the setpoint.
Tolerance works as shown in this diagram:
If you enter a positive tolerance, the process is out of tolerance when the
PV goes above the setpoint plus the tolerance.
If you enter a negative tolerance, the process goes out of tolerance when
the PV goes below the setpoint minus the tolerance.
Selectable Values:
-99 to 99, or Off (no tolerance).
Ending a Profile
Use this menu to make a segment the last one in the profile.
Selectable Values:
No or Yes.
Repeating a Profile
Use this menu to set the number of times you want a profile to repeat or
cycle.
Selectable Values:
1-99, or C (continuous cycling).
Positive Tolerance Value Ne
g
ative Tolerance Value
PV out of tolerance
PV within tolerance
Setpoint
PV out of tolerance
PV within tolerance
Setpoint
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
A SEGMENT 01
SEG TOLERNCE?OFF
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
A SEGMENT 01
LAST SEGMENT? NO
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
A REPEAT CYCLES
? 1