Seitenansicht 78
Setup
CLS Users Guide 71
Input Type
Use this menu to configure the input sensor for each loop as one of these
input types:
Thermocouple types (J, K, T, S, R, B and E).
RTD (4 and 8CLS). Two ranges: RTD1 (Platinum Class A) and
RTD2 (Platinum Class B).
Linear inputs.
Skip (an input type available for unused channels.) The scanning dis-
play doesn't show loops you've set to Skip.
The following tables show the input types and ranges.
Input Type
Range in
º
F Range in
º
C
* Accuracy:
25
º
C
Ambient
* Accuracy:
0-50
º
C Full
Temp. Range
º
C
º
C
º
F
º
C
º
F
J T/C -350 to 1400 -212 to 760
±
0.5
±
0.9
±
1.1
±
2.0
K T/C -450 to 2500 -268 to 1371
±
0.6
±
1.2
±
1.35
±
2.7
T T/C -450 to 750 -268 to 399
±
1.3
±
2.4
±
2.9
±
5.4
S T/C 0 to 3200 -18 to 1760
±
2.5
±
4.5
±
5.6
±
10.1
R T/C 0 to 3210 -18 to 1766
±
2.5
±
4.5
±
5.6
±
10.1
B T/C 150 to 3200 66 to 1760
±
6.6
±
12.0
±
14.9
±
27.0
E T/C -328 to 1448 -200 to 787
Pulse 0-2 KHz
Skip Loop is not scanned or displayed
Linear See the Linear Scaling section
* True for 10% to 100% of span.
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
01 INPUT
TYPE ? J T/C