Setup
8LS User’s Guide 71
Low Deviation Alarm Output Number
Use this menu to assign a digital output which activates when the loop is
in low diviation alarm.
Selectable values:
0-30.
Low Process Alarm Setpoint
Use this menu to set a low process alarm setpoint. The low process
alarm activates when the process variable (PV) goes below the low
process alarm setpoint. It deactivates when the PV goes above the low
process alarm setpoint plus the deadband.
Selectable values:
Any value within the input sensor’s range.
Low Process Alarm Status
Use this menu to enable or disable the low process alarm.
Selectable values:
On, Off.
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT STATUS OUTPUT%
1 LO DEV
OUTPN ? 0
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT STATUS OUTPUT%
1 ALARMS
LP? 0
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT STATUS OUTPUT%
1 ALARMS
LP? OFF