70 8LS Users Guide
Setup
Deviation Band Alarm
Use this menu to set the deviation bandwidth, a positive and negative
alarm point relative to the setpoint. If the setpoint changes, the alarm
points also changes. You can assign a separate digital output to the high
and low deviation alarm setpoints. (For example, the high deviation
alarm turns on a fan, and a low deviation alarm turns on a heater.
Selectable values: 0-255.
Deviation Band Alarm Status
Use this menu to set the deviation alarm status. You can enable or
disable the alarm function.
Selectable values:
On , Off.
High Deviation Alarm Output Number
Use this menu to assign a digital output which activates when the loop is
in high deviation alarm.
Selectable values:
0-30.
NOTE
All digital outputs are "OR’ed" together (com-
bined). Therefore, you can assign more than one
alarm to the same output number, and that output
will be On if any of those alarms is On.
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT
STATUS
OUTPUT%
1 ALARMS
DEV ? 10
1234 56 78
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUTPUT%
1 ALARMS
DEV ? OFF
1234 56 78
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUTPUT%
1 HI DEV
OUTPN? 0