Watlow 8LS Controller Bedienungsanleitung Seite 68

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 140
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 67
60 8LS Users Guide
Setup
Heat/Cool PB
Use this menu to set the Proportional Band.
Heat/Cool TI
Use this menu to set the Integral Term.
Selectable range:
0-5000 seconds.
Heat/Cool TD
Use this menu to set the Derivative constant.
Selectable range:
0-255 seconds.
Heat/Cool Output Filter
Use This menu to dampen the heat or cool outputs response. The output
responds to a step change by going to approximately 2/3 of its final
value within the number of scans you set here.
Selectable range:
0-255.
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT
STATUS
OUTPUT%
1 CONTROL
PB
H
T
?
50
1234 56 78
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUTPUT%
1 CONTROL
TI
? 180
H
T
1234 56 78
LOOP PROCESS UNITS
ALARM
SETPOINT
STATUS
OUTPUT%
1 CONTROL
TD ? 0
H
T
1234 56 78
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUTPUT%
1 CONTROL
FIL ? 2
H
T
Seitenansicht 67
1 2 ... 63 64 65 66 67 68 69 70 71 72 73 ... 139 140

Kommentare zu diesen Handbüchern

Keine Kommentare