Watlow Series SD 57 Chapter 10 Profiling
Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
N/A File Running
File number that is currently running.
1 to 4 1 900 R Profile is running.
N/A
Step Running
Step number that is currently running.
1 to 10 1 901 R Profile is running.
[EnSP]
[EnSP]
End Set Point Value
Set point value reached at the end of the
current step.
[sp;lo] to [sphi]
*902, 903 R Profile is running.
[hour]
[hour]
Hours Remaining
Indicates number of hours remaining in
the step currently running.
0 to 99 904 R Profile is running.
Active if the value
set for [ptyp] is
[``ti] or time
based profiles.
[Min]
[~Min]
Minutes Remaining
Indicates number of minutes remaining
in the step currently running.
0 to 59 905 R Profile is running.
Active if the value
set for [ptyp] is
[``ti] or time
based profiles.
[`SEc]
[ SEc]
Seconds Remaining
Indicates number of seconds remaining
in the step currently running.
0 to 59 907 R Profile is running.
Active if the value
set for [ptyp] is
[``ti] or time
based profiles.
[rAte]
[rAtE]
Ramp Rate
Rate at which the profile changes in de-
grees or units per minute.
0.0 to 9999.9 (0 to
9999900)
*907, 908 R Profile is running.
Active if the value
set for [ptyp] is
[rate] or rate
based profiles.
[Ent1]
[Ent1]
Event Output 1 status
Indicates Event Output 1 status.
[`Off] (0)
[``On] (1)
909 R Profile is running.
Output 1 is set to
[Ent1].
[Ent2]
[Ent2]
Event Output 2 status
Indicates Event Output 2 status.
[`Off] (0)
[``On] (1)
910 R Profile is running.
Output 2 is set to
[Ent2].
[Ent3]
[Ent3]
Event Output 3 status
Indicates Event Output 3 status.
[`Off] (0)
[``On] (1)
911 R Profile is running.
Output 3 is set to
[Ent3]
[WPr]
[WPr]
Wait-for Process Value
Profile clock waits until the process value
matches the Wait-for value and then con-
tinues with the step.
[sp;lo] to [sphi]
*912, 913 R Profile is run-
ning. [WF;P] set to
[~YEs].
[`EJC]
[ EJC]
Elapsed Jump Count
Number of times the profile has been
through the Jump Loop Step.
0 to 9999 (0 to 9999000) 914 R Profile is running
and the current
profile step running
is a Jump Loop Step
Type.
N/A Failed File Number
Indicates the file number that failed the
Pre-Run check.
1 to 4 365 R Profile State is set
to 3 (Pre-Run Failed
Start) or 4 (Pre-Run
Failed Resume)
N/A Failed Step Number
Indicates the step number that failed the
Pre-Run check.
1 to 10 366 R Profile State is set
to 3 (Pre-Run Failed
Start) or 4 (Pre-Run
Failed Resume)
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature pa-
rameters are in °F through Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.
Monitoring Profile Status from Modbus