Watlow Series SD 49 Chapter 10 Profiling
Display Parameter name
Description
Set-
tings
Range
(Integer values for Mod-
bus in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
[SoaH] Soak Step
[hour]
[hour]
Hours
The number of hours, (plus Min and
Sec parameters) equal the total soak
step time at set point under the
[soaH]
step type.
0 to 99 0 See page 53. Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
[Min]
[Min]
Minutes
The number of minutes, (plus Hour
and Sec parameters) equal the total
soak step time at set point under
the
[soaH]
step type.
0 to 59 0 See page 53. Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
[`SEc]
[ SEc]
Seconds
The number of seconds, (plus Hour
and Min parameters) equal the total
soak step time at set point under
the
[soaH]
step type.
0 to 59 0 See page 53. Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
[Ent1]
[Ent1]
Event Output 1
Selects whether Event Output 1 is
on or off during the program step.
[`Off] (0)
[``On] (1)
[`Off] (0)
See page 53. Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
Output 1 is set to
[Ent1].
[Ent2]
[Ent2]
Event Output 2
Selects whether Event Output 2 is
on or off during the program step.
[`Off] (0)
[``On] (1)
[`Off] (0)
See page 53. Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
Output 2 is set to
[Ent2].
[Ent3]
[Ent3]
Event Output 3
Selects whether Event Output 3 is
on or off during the program step.
[`Off] (0)
[``On] (1)
[`Off] (0)
See page 53. Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
Output 3 is set to
[Ent3].
[WF;P]
[WF.P]
Wait-for Process Enable
Select to enable Wait-for Process
value.
[`~no] (0)
[`YES] (1)
[`~no] (0)
See page 53. Profiling version only.
[WPr]
[WPr]
Wait-for Process Value
The program will not begin to decre-
ment the soak time during the pro-
grammed step until process value is
equal to the Wait-for Process Value
setting. Once the Wait-for Process is
satisfied, this function is no longer
active for this step.
-1999 to 9999
(-1999000 to
9999000)
75 See page 53. Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature
parameters are in °F through Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.