Watlow Series SD 47 Chapter 10 Profiling
The Profiling Page allows you to enter your ramp and soak profile information. To go to the Profiling Page from the
Home Page, press the Advance Key
and
[Prof]
appears in the lower display. Press the Up Key
¿
to change the
upper display to
[~yes]
.
• Press the Advance Key to move through the profile parameter prompts.
• Press the Up ¿ or Down ¯ keys to change the profile parameter values.
• Press the Infinity Key ˆ at any time to return to the Home Page.
Note: The Profiling Page only appears if the profiling version has been ordered (SD_R- _ _ _ _- _ _ _ _ ).
Note: The Profiling Page is only accessible if the profile is on hold or not running.
[File] File
[step} Step
[Styp} Step Type
[Stpt] Set Point Step [soaH] Soak Step [``JL] Jump Loop Step {Lfil] Link File Step [`EnD] End Step (End)
[tg;SP] Target Set Point [hour] Hour [``JF] Jump File {~~LF] Link File [`EnD] Select End Typ
e
[hour] Hour* [min] Minutes [``JS] Jump Step
[min] Minutes* [`seC] Seconds [``JC] Jump Count
[`seC] Seconds* [ent_] Event Outputs 1-3
[rate] Rate** [wF;P} Wait-for Process Enablev
[ent_] Event Outputs 1-3 [wPr} Wait-for Process Value
[Prof] = [~Yes]
* Hour, minutes and seconds appear if Profile Type [PtYP] is set to [~~ti].
** Rate appears if Profile Type
[PtYP] is set to [rAtE].
The Profiling Menu
Display Parameter name
Description
Set-
tings
Range
(Integer values for Mod-
bus in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
[FiLe]
[FiLE]
File
Represents the profile to be edited
or viewed.
[```1] (1)
[```2] (2)
[```3] (3)
[```4] (4)
1 See page 53. Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
[StEP]
[StEP]
Step
Represents the current step of the
profile to be edited or viewed. Up to
ten steps per file.
[```1] (1)
• thru
[``10] (10)
1 See page 53. Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
[StYp]
[StYP]
Step Type
Select from five different step types.
[`end] End (0)
[stpt] Set Point (1)
[soaH] Soak (2)
[``jl] Jump Loop (3)
[LFil] Link File (4)
[`end] (0)
See page 53. Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature
parameters are in °F through Modbus.