Watlow EZ-ZONE
®
RML Module • 70 • Chapter 4 Setup Page
RM Limit Module • Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`s2;E]
[ SZ.E]
Math (1 to 16)
Source Zone E
Set the zone of the function
selected above.
0 to 16 0 3538
[offset 70]
0x7D
(125)
1 to 16
0xF (15)
- - - - 25015 uint
RWES
[`S;Lo]
[ S.Lo]
Math (1 to16)
Input Scale Low
This value will correspond
to Output Range Low.
-1,999.000 to 9,999.000 0.0 3556
[offset 70]
0x7D
(125)
1 to16
0x18 (24)
129 25024 float
RWES
[`S;hi]
[ S.hi]
Math (1 to 16)
Input Scale High
This value will correspond
to Output Range High.
-1,999.000 to 9,999.000 1.0 3558
[offset 70]
0x7D
(125)
1 to 16
0x19 (25)
130 25025 float
RWES
[`r;Lo]
[ r.Lo]
Math (1 to 16)
Output Range Low
This value will correspond
to Input Scale Low.
-1,999.000 to 9,999.000 0.0 3560
[offset 70]
0x7D
(125)
1 to 16
0x1A (26)
131 25026 float
RWES
[`r;hi]
[ r.hi]
Math (1 to 16)
Output Range High
This value will correspond
to Input Scale High.
-1,999.000 to 9,999.000 1.0 3562
[offset 70]
0x7D
(125)
1 to 16
0x1B (27)
132 25027 float
RWES
[p;unt]
[P.unt]
Math (1 to 16)
Pressure Units
[`psi] Pressure Units (1671)
[mbr] mbar (1672)
[torr] Torr (1673)
[pasc] Pascal (1674)
[atm] Atmosphere (1675)
Pressure
Units
3568
[offset 70]
0x7D
(125)
1 to 16
0x1E (30)
- - - - 25030 uint
RWES
[a;unt]
[A.unt]
Math (1 to 16)
Altitude Units
.
[``ft] Feet (1674)
[`Hft] Kilofeet (1671)
Kilofeet 3570
[offset 70]
0x7D
(125)
1 to 16
0x1F (31)
- - - - 25031 uint
RWES
[`FiL]
[ FiL]
Math (1 to 16)
Filter
Filtering smooths out the
output signal of this func-
tion block. Increase the
time to increase filtering.
0.0 to 60.0 seconds 0.0 3564
[offset 70]
0x7D
(125)
1 to 16
0x1C (28)
- - - - 25028 float
RWES
[`uAr]
[`Set]
Variable Menu
[tyPE]
[tyPE]
Variable (1 to 16)
Data Type
Set the variable's data
type.
[AnLg] Analog (1215)
[`Dig] Digital (1220)
Analog 9110
[offset 20]
0x66 (102)
1 to 16
1
210 2001 uint
RWES
[Unit]
[Unit]
Variable (1 to 16)
Units
Set the variable's units.
[`A;tp] Absolute Temperature
(1540)
[`r;tp] Relative Temperature
(1541)
[PWr] Power (73)
[`Pro] Process (75)
[``rh] Relative Humidity
(1538)
[nonE] None (61)
Absolute
Temper-
ature
9122
[offset 20]
0x66 (102)
1 to 16
7
- - - - 2007 uint
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set