Watlow EZ-ZONE
®
RML Module • 52 • Chapter 4 Setup Page
RM Limit Module • Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`iP;1]
[ ip.1]
Linearization (1 to 16)
Input Point 1
Set the value that will be
mapped to output 1.
-1,999.000 to 9,999.000 0.0 8004
[offset 70]
0x86 (134)
1 to 0x10
(16)
8
157 34008 float
RWES
[`oP;1]
[ op.1]
Linearization (1 to 16)
Output Point 1
Set the value that will be
mapped to input 1.
-1,999.000 to 9,999.000 0.0 8024
[offset 70]
0x86 (134)
1 to 0x10
(16)
0x12 (18)
158 34018 float
RWES
[`iP;2]
[ ip.2]
Linearization (1 to 16)
Input Point 2
Set the value that will be
mapped to output 2.
-1,999.000 to 9,999.000 1.0 8006
[offset 70]
0x86 (134)
1 to 0x10
(16)
9
159 34009 float
RWES
[`oP;2]
[ op.2]
Linearization (1 to 16)
Output Point 2
Set the value that will be
mapped to input 2.
-1,999.000 to 9,999.000 1.0 8026
[offset 70]
0x86 (134)
1 to 0x10
(16)
0x13 (19)
160 34019 float
RWES
[`iP;3]
[ ip.3]
Linearization (1 to 16)
Input Point 3
Set the value that will be
mapped to output 3.
-1,999.000 to 9,999.000 2.0 8008
[offset 70]
0x86 (134)
1 to 0x10
(16)
0xA (10)
161 34010 float
RWES
[`oP;3]
[ op.3]
Linearization (1 to 16)
Output Point 3
Set the value that will be
mapped to input 3.
-1,999.000 to 9,999.000 2.0 8028
[offset 70]
0x86 (134)
1 to 0x10
(16)
0x14 (20)
162 34020 float
RWES
[`iP;4]
[ ip.4]
Linearization (1 to 16)
Input Point 4
Set the value that will be
mapped to output 4.
-1,999.000 to 9,999.000 3.0 8010
[offset 70]
0x86 (134)
1 to 0x10
(16)
0xB (11)
163 34011 float
RWES
[`oP;4]
[ op.4]
Linearization (1 to 16)
Output Point 4
Set the value that will be
mapped to input 4.
-1,999.000 to 9,999.000 3.0 8030
[offset 70]
0x86 (134)
1 to 0x10
(16)
0x15 (21)
164 34021 float
RWES
[`iP;5]
[ ip.5]
Linearization (1 to 16)
Input Point 5
Set the value that will be
mapped to output 5.
-1,999.000 to 9,999.000 4.0 8012
[offset 70]
0x86 (134)
1 to 0x10
(16)
0xC (12)
165 34012 float
RWES
[`oP;5]
[ op.5]
Linearization (1 to 16)
Output Point 5
Set the value that will be
mapped to input 5.
-1,999.000 to 9,999.000 4.0 8032
[offset 70]
0x86 (134)
1 to 0x10
(16)
0x16 (22)
166 34022 float
RWES
[`iP;6]
[ ip.6]
Linearization (1 to 16)
Input Point 6
Set the value that will be
mapped to output 6.
-1,999.000 to 9,999.000 5.0 8014
[offset 70]
0x86 (134)
1 to 0x10
(16)
0xD (13)
167 34013 float
RWES
[`oP;6]
[ op.6]
Linearization (1 to 16)
Output Point 6
Set the value that will be
mapped to input 6.
-1,999.000 to 9,999.000 5.0 8034
[offset 70]
0x86 (134)
1 to 0x10
(16)
0x17 (23)
168 34023 float
RWES
[`iP;7]
[ ip.7]
Linearization (1 to 16)
Input Point 7
Set the value that will be
mapped to output 7.
-1,999.000 to 9,999.000 6.0 8016
[offset 70]
0x86 (134)
1 to 0x10
(16)
E (14)
169 34014 float
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User