Watlow EZ-ZONE
®
RML Module 43 Chapter 4 Setup Page
RM Limit Module Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[``Ai]
[`Set]
Analog Input Menu
[`Sen]
[ SEn]
Analog Input (1 to 12)
Sensor Type
Set the analog sensor type
to match the device wired
to this input.
Note:
There is no open-sensor
detection for process
inputs.
[`oFF] Off (62)
[``tC] Thermocouple (95)
[`mu] Millivolts (56)
[uolT] Volts dc (104)
[`MA]
Milliamps dc (112)
[r0;1H] RTD 100 Ω (113)
[r1;0H] RTD 1,000 Ω (114)
[`Pot] Potentiometer 1 kΩ
(155)
[thEr] Thermistor (229)
418
[offset 90]
0x68 (104)
1 to 0xC
(12)
5
3 4005 uint
RWES
[`Lin]
[ Lin]
Analog Input (1 to 12)
Linearization
Set the linearization to
match the thermocouple
wired to this input.
[```b] B (11) [```H] K (48)
[```C] C (15) [```n] N (58)
[```d] D (23) [```r] R (80)
[```E] E (26) [```S] S (84)
[```F] F (30) [```t] T (93)
[```J] J (46)
J
420
[offset 90]
0x68 (104)
1 to 0xC
(12)
6
4 4006 uint
RWES
[Unit]
[Unit]
Analog Input (1 to 12)
Units
Set the type of units the
sensor will measure.
[`A;tP] Absolute Temperature
(1540)
[PWr] Power (73)
[`Pro] Process (75)
[``rh] Relative Humidity
(1538)
Process 492
[offset 90]
0x68 (104)
1 to 0xC
(12)
0x2A (42)
5 4042 uint
RWES
[`S;Lo]
[ S.Lo]
Analog Input (1 to 12)
Scale Low
Set the low scale for pro-
cess inputs. This value,
in millivolts, volts or mil-
liamps, will correspond to
the Range Low output of
this function block.
-100.0 to 1,000.0 0.0 438
[offset 90]
0x68 (104)
1 to 0xC
(12)
0xF (15)
6 4015 float
RWES
[`S;hi]
[ S.hi]
Analog Input (1 to 12)
Scale High
Set the high scale for pro-
cess inputs. This value,
in millivolts, volts or mil-
liamps, will correspond to
the Range High output of
this function block.
-100.0 to 1,000.0 20.0 440
[offset 90]
0x68 (104)
1 to 0xC
(12)
0x10 (16)
7 4016 float
RWES
[`r;Lo]
[ r.Lo]
Analog Input (1 to 12)
Range Low
Set the low range for this
function block's output.
-1,999.000 to 9,999.000 0.0 442
[offset 90]
0x68 (104)
1 to 0xC
(12)
0x11 (17)
8 4017 float
RWES
[`r;hi]
[ r.hi]
Analog Input (1 to 12)
Range High
Set the high range for this
function block's output.
-1,999.000 to 9,999.000 9,999.0 444
[offset 90]
0x68 (104)
1 to 0xC
(12)
0x12 (18)
9 4018 float
RWES
[`P;EE]
[ P.EE]
Analog Input (1 to 12)
Process Error Enable
Turn the Process Error
Low feature on or off.
[`off] Off (62)
[Low] Low (53)
Off 468
[offset 90]
0x68 (104)
1 to 0xC
(12)
0x1E (30)
10 4030 uint
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set