Watlow CLS200 Bedienungsanleitung Seite 97

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 251
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 96
CLS200 Series User’s Guide Chapter 4: Setup
Doc.# 0600-3050-2000 Watlow Anafaze 81
AC Line Frequency
Specify the ac line frequency. Since the controller reduces
the effect of power line noise on the analog measurement by
integrating the signal over the period of the ac line frequen-
cy, the controller must know the frequency of power in use.
You must switch power to the controller off, then back on,
to make a change to this parameter take effect.
Selectable values: 50 or 60 Hz.
Digital Output Polarity on Alarm
Set the polarity of all digital outputs used for alarms. If LOW
is selected, if an alarm occurs the outputs sink to analog
common. If HIGH is selected, the outputs sink to common
when no alarm is active and go high when an alarm occurs.
Selectable values: HIGH or LOW.
This parameter does not affect the Global Alarm output or
the Watchdog Alarm output.
EPROM Information
The display shows the controller type, firmware options,
the firmware version and the EPROM checksum. Table 4.4
lists the available firmware options.
Table 4.4 Firmware Option Codes
Firmware Option Description
(none) Standard Firmware
-EF Enhanced Features Option
-RS Ramp/Soak Option
-EX Extruder Option
ALARM
AC LINE FREQ ?
60 HERTZ
ALARM
DIG OUT POLARITY ON
ALARM ? LOW
ALARM
CLS208-RS
V03.13 CS=ED74
Firmware Option
EPROM Checksum
Firmware Version
Controller Model
Seitenansicht 96
1 2 ... 92 93 94 95 96 97 98 99 100 101 102 ... 250 251

Kommentare zu diesen Handbüchern

Keine Kommentare