Chapter 6: Enhanced Features CLS200 Series User’s Guide
130 Watlow Anafaze Doc.# 0600-3050-2000
Table 6.4 Application Example: Setting Up
Remote Setpoint
4. Press
BACK
several times until the normal loop display
appears. The setpoint of loop 2 will now be equal to the
process variable of loop 1.
5. To complete the remote analog setpoint setup, loop 1
may be configured for outputs and alarms. Likewise,
loop 2 must be configured for inputs, outputs, and
alarms. See Chapter 4, Setup for information on loop
setup.
Display User Input
Press
YES
to set up the ratio control parameters for loop 2.
Assign loop 01 to be the master loop. Press
ENTER
.
Enter the minimum ratio loop setpoint. For this example, we will
use 0° F. Press
ENTER
.
Enter the maximum ratio loop setpoint. For this example, we will
use 300.0° F as a maximum. Press
ENTER
.
Enter the control ratio, which is the multiple applied to the master
process variable. In this example the ratio is 1.0. Press
ENTER
.
Enter the setpoint differential (or offset). For this example we have
no offset requirement and will use 0. Press
ENTER
.
ALARM
SETUP LOOP 02
RATIO CONTROL?
ALARM
02 RATIO CONTROL
MSTR LOOP? 01
ALARM
02 RATIO CONTROL
MIN SP? 0
ALARM
02 RATIO CONTROL
MAX SP? 300.0
ALARM
02 RATIO CONTROL
CTRL RATIO? 1.0
ALARM
02 RATIO CONTROL
SP DIFF.? 0