PPC-2000 User’s Guide Chapter 3: Operating with AnaWin 3
Doc.# 30002-00 Rev 2.3 Watlow Anafaze 101
Linear 0-10Vdc Input Example
For a sensor that measures pressures from 0.0 to 15.0 psia and
outputs a 0-10Vdc signal, set the following parameters:
Table 3.5 Scaling Parameters for 0-10Vdc
Linear Input Example
Linear 4-20mA Input Example
For a sensor that measures relative humidity with a range of
0.00 to 100.00% and outputs a 4-20mA signal, set the
parameters according to Table 3.6.
Table 3.6 Scaling Parameters for 4-20mA Linear
Input Example
Parameter Setting Units
Input Type Linear -1 to 10 (v)
Units psia
Input Signal Lo 0.000 V
Input Signal Hi 10.000 V
PV Lo 0.0 psia
PV Hi 15.0 psia
Decimal Places 1
Parameter Setting Units
Input Type Linear -2 to 20 (mA)
Units %
Input Signal Lo 4.000 mA
Input Signal Hi 20.000 mA
PV Lo 0.00 %
PV Hi 100.00 %
Decimal Places 2