Watlow Series SD6 PID with DeviceNet ■ 31 ■
Table 38. Profile Program Class Attributes
Instances 1 through 10 are for File 1, steps 1 through 10.
Instances 11 through 20 are for File 2, steps 1 through 10.
Instances 21 through 30 are for File 3, steps 1 through 10.
Instances 31 through 40 are for File 4, steps 1 through 10.
Table 39. Profiling Object Instance Attributes
Attribute # Access Rule Name DeviceNet
Data Type
Description of Attribute Semantics of Values
100 Get/Set Step Type USINT Selects step type (0) - End (default)
(1) - Set Point
(2) - Soak
(3) - Jump Loop
(4) - Link File
101 Get/Set Target Set Point DINT Indicates ending set point
value
-1999 to 9999 (*1000)
(default = 75)
102 Get/Set Hours UINT Hours in the step 0 to 99.
(default = 0)
103 Get/Set Minutes UINT Minutes in the step 0 to 59.
(default = 0)
104 Get/Set Seconds UINT Seconds in the step 0 to 59.
(default = 0)
105 Get/Set Rate UDINT Indicates rate at which set
point changes in degrees per
minute
0 to 9999 (*1000)
(default = 0)
106 Get/Set Event Output 1 BOOLEAN Selects whether output 1 is
on or off during step
(0) - OFF (default)
(1) - ON
Attribute # Access
Rule
Name DeviceNet
Data Type
Description of Attribute Semantics of Values
1 Get Revision UINT Revision of this object The revision level of this
object (currently 1)
2 Get Max Instance UINT Max allowed Instances of this
object
Always 1 for this Class
Kommentare zu diesen Handbüchern