Silver Series EM Operator Interface
Terminals
Addendum to EZwarePlus Programming Manual
Operator Interface Terminals
1241 Bundy Boulevard, Winona, Minnesota USA 55987
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507 http://www.watlow.com
0600-0102-0000 Rev. A ©2014 Watlow. All rights reserved.
April 2014
Seitenansicht 0
1 2 3 4 5 6 ... 49 50

Inhaltsverzeichnis

Seite 1 - Operator Interface Terminals

Silver Series EM Operator Interface Terminals Addendum to EZwarePlus Programming Manual Operator Interface Terminals 1241 Bundy Boulevard, Wino

Seite 2 - Table of Contents

In such a system the Silver Series EM OIT is connected to and configured to communicate with the gateway. The gateway presents itself as a single devi

Seite 3 - Chapter 1: Introduction

Chapter 4: Programming Tutorials The following sections guide you through creating a first project using EZwarePlus and a Silver Series EM OIT that co

Seite 4

6) In the System Parameter Settings dialog, under the Device List, click New… (002) 7) For PLC type, choose the appropriate driver. See the table

Seite 5

For part numbers like… with… For PLC type choose… For PLC I/F choose… PMxxxxx-2xxxxxx EZKx-2xxx-xxxx RMAx-x2xx-xxxx Modbus RTU Modbus RTU Master

Seite 6 - Chapter 3: Communications

14) To set up communications with controllers connected to other COM ports or to configure additional controllers communicating via Ethernet: • Clic

Seite 7 - Address Maps

4) Ensure the Name is Window_011 and the Window no. is 11. 5) Set Width to 420. 6) Set Height to 300 (272 for the 4.3 in. OIT). 7) To set the back

Seite 8

5) For PLC name choose the Modbus Master or Modbus TCP/IP Master. 6) For Device type choose 4x. (075) 7) For Address enter the address of the heat

Seite 9 - Access Modules

10) Click the Outline tab. 11) In Degree set Start degree to 270. 12) In Degree set End degree to 90. 13) In Background uncheck Full circle. 14)

Seite 10 - Important Things to Know

27) Double-click the meter to open the Meter Display Object’s Properties dialog. 28) Click the Profile tab. 29) Set X to 140. 30) Set Y to 60. 31)

Seite 11 - Tutorials

6) On the Numeric Format tab. 7) In Data format set the data type. See the table. 8) On the Font tab set Align to Right. 9) Click OK. (013b) For

Seite 12 - (002)

Table of Contents Chapter 1: Introduction ... 3 Additional Resources .

Seite 13

Add Increment and Decrement Buttons This example assumes you have created a window in a project that is configured to communicate with a Watlow Contro

Seite 14 - Create a Popup Window

16) Click Shape Library… 17) Click the new library icon Select Lib… 18) In the EZwarePlus program’s library directory (typically: C:\Watlow\EZPlus

Seite 15 - (009)

To add a button that decrements the set point: 1) Click the increment button to select it. 2) From the Edit menu, choose Copy. 3) From the Edit men

Seite 16

Add an Option List for Control Mode This example assumes you have created a window in a project that communicates with a Watlow Controller and that wi

Seite 17

8) In the Values column type the numeric and in the Item data the text that corresponds to each option you want to include. See the table. 9) Click

Seite 18 - Add a Numeric Display

Add a Button to Close the Popup Window This example assumes you have created a window in a project that communicates with a Watlow Controller and that

Seite 19 - (013b)

16) Click the Profile tab 17) Set Position X to 375. 18) Set Position Y to 5. 19) Set Size Width to 40. 20) Set Size Height to 40. 21) Click OK.

Seite 20

6) Position the cursor centered in the top third of the window layout and click to place the text. 7) From the File menu choose Save. Add a Numeric

Seite 21

11) Move the cursor with the outline to position the display field in the center of the screen and click to place it. 12) From the File menu choose

Seite 22

18) Click OK. 19) Position the cursor and click to place the function key. 20) From the File menu choose Save. (032) Compile and Download the Proj

Seite 23

Chapter 1: Introduction The Silver Series EM Operator Interface Terminals (OITs) are powerful human machine interfaces for equipment and processes. EZ

Seite 24

To download via Ethernet: 1) Determine the OIT’s IP address: • If you don’t already know the OIT’s IP address, follow the instructions in Determinin

Seite 25

To download the project via a USB drive to an OIT: 1) Connect at USB drive to the PC 2) From the Tools menu choose Build Data for USB Disk or SD Car

Seite 26 - Edit the Startup Window

3) With the Virtual Keyboard enter the Password. (By default this is 111111.) Note: If you have difficulty entering the password, see the hints below

Seite 27

• In Comment type a description of the data to be copied such as “PV 1”. • For Address type choose Word. • For Interval choose a value that is the

Seite 28

3) Click Exit to close the Data Transfer (Time-based) Object window. (043) To set up data sampling to log the data: 1) On the Objects menu, click D

Seite 29

8) In Read address Address type the first address to which data was copied. In the example, this is 200. 9) In Max. data records type the number of

Seite 30

15) Click OK to close the Data Sampling Object set up window. 16) Click Exit to close the Data Sampling Object window. (050) Silver Series EM OIT

Seite 31

Create a Graph This example assumes you have a project with at least one controller and that you have previously configured a time-based data sampling

Seite 32 - Log Data

7) Edit the Comment to read Trend Graph Window. 8) Choose Change full-screen window. 9) For Window no. choose 12. Trend. (066) 10) Click the Labe

Seite 33

4) For Trend type choose Real-time. 5) For Distance between data samples/X axis time range choose Time. 6) In Distance type the number of seconds t

Seite 34

Chapter 2: Install and Wiring Consult the Watlow Silver Series EM Installation Guide for detailed information on installing and wiring the OITs. This

Seite 35

12) Place and size the trend object. (053) 13) Optional: In the Trend Display Object Properties dialog Trend tab enable the Grid and set it up to di

Seite 36

Use Recipes This example assumes you have a project with at least one controller in which the recipe memory has not already been used for something el

Seite 37 - Create a Graph

1) From the Objects menu choose Data Transfer (Trigger-based). 2) In Comment type “Recipe Save:” and the name of the name of the parameter (such as

Seite 38

11) Click OK to close the Address dialog 12) For Mode choose External Trigger. 13) For Trigger address PLC name choose the OIT (Local HMI by defaul

Seite 39

1) From the Objects menu choose Data Transfer (Trigger-based). 2) In Description type “Recipe Load:” and the name of the parameter (such as “Loop 1

Seite 40

To create a button to trigger the data transfer objects to copy the values currently in the controller to the corresponding recipe memory in the OIT:

Seite 41 - Use Recipes

Optional: To see what you are copying from the controller to the OIT’s recipe memory, create an object displaying the current value in the controller

Seite 42

Address indexing allows a screen object to display and set the value of different memory locations depending on the value in the index. In this exampl

Seite 43

To select the recipe to save to or load from create a multi-state switch to select the recipe as follows: 1) On the Objects menu point to Buttons and

Seite 44

17) Click Setting… 18) For each state enter the appropriate offset Value. For state 0 enter 0. For state 1 enter a value that will offset the begin

Seite 45

• The IP address is listed in the System settings window on the Network tab. (If Auto Get IP Address is selected, the IP Address is not editable. If

Seite 46

Silver Series EM OIT  50  Watlow Addendum

Seite 47

Chapter 3: Communications Basics The Silver Series EM OIT can communicate with Watlow controllers via Modbus TCP or Modbus RTU. This section defines t

Seite 48

supply “the addresses.” So to use any two products together you need to know whether or not you have to convert the specified “address” in order to ge

Seite 49

For example, the EZ-ZONE PM Integrated Controller Models User’s Manual lists Map1 and Map 2 addresses for Process Value for Analog Inputs 1 and 2. If

Seite 50

ZONE controllers via Ethernet, add three Modbus TCP/IP Master devices to the device list in the System Parameter Settings dialog each configured to co