Watlow Series PD ■ 11 ■ Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Note: Current transformer (CT)
must be purchased separately.
Note: A current transformer input
cannot be associated with a
process output on Output 1 or 3.
Note: Install a 1kΩ pull-down
resistor for each digital in-
put using voltage inputs.
Note: Install a 10kΩ pull-up re-
sistor for each digital input
using contact closure in-
puts.
Figure 11a — Three Phase using Two Current Transformers
One Digital Input and One Current Transformer Input
PD_ 2-_ _ _ _-_ _ _
Digital Input 1
• Input impedance 10kΩ, dc only
Figure 11b — Voltage input
0-1VÎ (dc) Event Input Low State
2-36VÎ (dc) Event Input High State
Figure 11c — Contact closure
0-2kΩ Event Input Low State
> 7kΩ Event Input High State