Setup
Setup Menu, Chapter 4 WATLOW Series 988LF Users Manual 4.5
[`rL1]
[`rH1]
Range Low and Range
High continued from
previous page.
NOTE:
The range high [`rH1]
value for process
inputs can be extended
to [9999].
Default Default Default Default
↓↓
``°F] [`°C]
[`rL1] [`rH1] [`rL1] [`rH1]
[```b] [``32][3300] [```0][1816]
[`rtd] [-328][1472] [-200][`800]
[`r†d] [-9(9][99(9] [-7#3][53&7]
process
[4-20] [-999][`999] units
[0-20] [-999][`999] units
[`0-5] [-999][`999] units
[`1-5] [-999][`999] units
[0-10] [-999][`999] units
[0-50] [-999][`999] units
RTD Calibration Curve
Select the RTD calibration curve. The RTD input uses either the
European (DIN, 0.003850 ohms/ohms/°C) or Japanese (JIS, 0.003916
ohms/ohms/°C) linearization standard.
[`rtd] This prompt appears only if you have set [`In1] to [`rtd] or
[`r†d].
Default
[`din] [`J15]
[`rtd [`rtd
[`rtd]