How to Use Data Communications
WATLOW Series 942
"?" Commands
Table 6 -
"? MTR" Command
Response Data.
< > = Non-literal
Description.
PtYP = rAtE PtYP = tI Step Type
Set Point Set Point Soak Jumploop End
Step # <Step#> <Step#> <Step#> <Step#> <Step#>
Type Code 1123 0
Data.2 <SP> <SP> <HOUr> <JS> <End>
Data.3 <rAtE> <HOUR> <min> <JC>
Data.4 <Ent1> <MIN> <SEC>
Data.5 <Ent2> <SEC> <Ent1>
Data.6 <Ent1> <Ent2>
Data.7 <Ent2>
"? MDL" Command
This command asks the 942 for the type of unit and the level of software. The
model number will appear as 1 character. The syntax of the function is as
follows:
? <Space> MDL
This function will return the following information:
942<Model number> <Space> <Software revision level>
"? MTR" Command
The ? MTR command monitors the current RUNning step.
The syntax for this command is: ?<Space> MTR
There are no arguments to the command. The command will return the
following data:
<Current Step #> <Space> <Current Step Type> <Space> Data.4 <Space>
Data.5 . . .Data.n
Table 6 below shows how to interpret the response syntax. Note that each
argument is an ASCII decimal number representing a specific value for each
parameter listed in the table. A response would be:
<11> <space> <1> <space> <375> <space> <2> <space> <30> <space> <0>
<space> <1> <space> <1>
This tells you that the current step is #11 a Set Point step, the SP is 375°. Step
time is 2:30:00, Events 1 and 2 (Ent1, Ent2) are ON.
Data.1 Data.2
Low Limit High Limit Code Function
TAG 0 7 0 - - - = no logging
1 - - A
2 - S -
3 - SA
4 P - -
5 P - A
6 PS -
7 PSA
Table 5 -
Continued
NOTE:
P = Process
S = Set Point
A = Auxiliary Status
- - - = no logging