Alarms & Error Codes, Chapter 5
14
WATLOW Series 733/734 Program Manual
Error Codes
Problem Probable Cause Solution
Er10 -
Stack overflow error
Er11 -
Zone 1 open sensor error
Er12 -
Zone 1 shorted sensor
Er13 -
Zone 2 Open sensor
Er14 -
Zone 2 shorted sensor
Er15 -
Zone 1 loop error
Er16 -
Zone 2 loop error
Microprocessor error
Open sensor
Incorrect sensor type
Measuring temperature
outside the sensor
range
Open sensor
Incorrect sensor type
Measuring temperature
outside the sensor
range
• Reversed sensor leads
Faulty heater or gas
valve
Shorted sensor
Faulty output switching
device
Blown fuse to heater
Incorrect Pb1 value
for thermal system
See Er15 Probable
Cause above.
Incorrect Pb2 value for
thermal system
Cycle power
Check the InP1 para-
meter. Verify it
matches your sensor.
Check the InP1 para-
meter. Verify it
matches your sensor.
Check the InP2 para-
meter. Verify it
matches your sensor.
Check the InP2 para-
meter. Verify it
matches your sensor.
Check heater or gas
valve
Check sensor
Check output switching
device
Check fuse to heater
Auto-tune the control
See Er15 Solution above.
Auto-tune the control
˜
NOTE:
For Er10 through
Er14, first check
the sensor and
connections for a
reversed or open
sensor before
trying the solution
listed.
˜
NOTE:
Er06 through Er09,
and Er11 through
Er14 are self
clearing errors if
the condition that
caused the alarm
has been taken
care of.
Table 2 -
Continued
Error Code Actions
Error codes will result in these conditons:
• The alarm outputs are in their alarm state (de-energized).
The display alternately flashes the process value and error code.
• All keys are inactive except for the Temperature key . This key snoozes the
error code and display for 30 seconds.
The above conditions occur regardless of the LOC value, or the presence of the
Setup, Service or Calibration Menus.
To clear a corrected error…
• Cycle power to the control.
OR
Enter the Program mode by pressing the keys simultaneously for
3 seconds.
Press the Menu 12 key
12
once.
Press the Time key . The EC (Error Clear) prompt is displayed.
Press the Temperature key , and the error is cleared. Press the Time key
twice, and you're back to the Operation mode [0)º0].