Watlow QPAC Modular SCR Power Control Service Bedienungsanleitung Seite 6

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 43
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 5
6 WATLOW QPAC Service Manual
Overview, Chapter 1
Specifications
QPAC Specifications
Operation
Modular control base with plug-in card and transformer
• Plug-in control cards
• Solid state contactor, AC or DC input
• Burst firing (zero cross) control, fixed or variable time base
Phase angle control with soft start and current limiting, or digital input
• Plug-in transformers (50/60Hz)
• 120 VAC operation
• 208/240 VAC operation
• 380 VAC operation
• 415 VAC operation
• 480 VAC operation
• 600 VAC operation, consult factory
Power bases
• Single phase (Q01), 1 pair of SCRs
• Three phase (Q32), 2 leg control, 2 pair SCRs.
Resistive load only, balanced or unbalanced, burst firing (zero cross) only
• Three phase (Q33), 3 pair hybrid SCRs/diodes
Recommended for phase angle only with balanced load.
Control Cards
(QCA) Solid state contactor, AC Input (08-5285)
• 120 VAC @ 30mA minimum
• AC signal input sources (ie., Triacs or mechanical relay outputs with noise
suppression) require customer supplied resistors across the power control
AC command signal input terminals to prevent false firing.
• 24 VAC input, 200/10 watts typical
• 120 VAC input, 1K/25 watts typical
• 240VAC input, two 1K/25 watts in series typical
(QCD) Solid state contactor, DC Input (08-5286)
• ON, 4 to 10VDC; OFF, 0VDC
• Built-in noise reduction network
(QBF) Burst firing (zero cross) control Fixed Time Base (08-5289)
• Process input factory set @ 4-20mA
• Input impedance 250 (clip resistor for 5Kvoltage input)
• Time Base 4 seconds (clip resistor for 1 sec)
(QBV) Burst firing (zero cross) control , Variable Time Base (08-5342)
• Process input factory set @ 4-20mA
• Input impedance 250 (clip resistor for 5Kvoltage input)
Bias and Gain card optional
(QAF) Phase angle control (08-5288)
• Process input factory set @ 4-20mA
• Input impedance 250 (clip resistor for 5Kvoltage input)
• Soft start 10 sec (approximately)
(QAL) Phase angle control with current limit: (08-5411)
Some heater elements change resistance during their operation, (i.e., silicon
carbide). In order to control at a slow ramp, it is often advantageous to limit the
current. Sensing the current is via a current transformer. This is NOT a means
of protecting the SCR.
• Process input factory set @ 4-20mA
• Input impedance 250 (move jumper for 5Kvoltage input)
• Soft start 10 sec (approximately)
• Current transformer included
Current Limiting.
(QAD) Phase angle control with digital input (08-5314)
• Remote digital phase control
• Interface, Centronics® parallel, 8 lines
• Power steps, 256
Seitenansicht 5
1 2 3 4 5 6 7 8 9 10 11 ... 42 43

Kommentare zu diesen Handbüchern

Keine Kommentare