Specifications:
(2346)
Control Mode
• Microprocessor-based, user selectable control modes
• Single input, single output
• Heat or cool auto-tuning
Output #1: User selectable
• ON/OFF; P, PI, PD, PID heat or cool action adjustable switching differential:
1 to 9999 or 0.1 to 999.9°F or °C
• Proportional band: 0 to 9999, or 0.0 to 999.9°F or °C
• Integral: 0.00 to 99.99 minutes per repeat
• Reset: 0.00 to 99.99 repeats per minute
• Derivative/Rate: 0.00 to 9.99 minutes
• Cycle Time: 0.1 to 60.0 seconds
Output #2: User selectable
• Process or deviation alarm with flashing alarm status indicator
• Alarm with separate high and low set points
• Hysteresis: 1 to 9999° switching differential
Operator Interface
• EIA-485 serial communications with Modbus
™
RTU protocol
• 9600, 19200 user selectable baud rates
• 1 to 63 user selectable address range
Sensor Input
• Sensor input sampling rate: 10 samples/second, 10Hz
• Thermocouple, grounded or ungrounded sensors
• RTD 2 or 3 wire, platinum, 100Ω@ 0°C calibration to JIS curve (0.003916Ω/Ω/°C), or
DIN curve (0.00385Ω/Ω/°C)
• Sensor break protection de-energizes control output to protect system or selectable
bumpless transfer to manual operation.
• °F or °C, user selectable
• Sensor Ranges:
Accuracy Ranges: Operating Ranges
B t/c 1598 to 3092°F 870 to 1700°C 32 to 3300°F 0 to 1816°C
C (W5) t/c 32 to 4200°F 0 to 2315°C 32 to 4200°F 0 to 2315°C
D (W3) t/c 32 to 4200°F 0 to 2315°C 32 to 4200°F 0 to 2315°C
E t/c -328 to 1472°F -200 to 800°C -328 to 1470°F -200 to 800°C
J t/c 32 to 1382°F 0 to 750°C 32 to 1500°F 0 to 815°C
K t/c -328 to 2282°F -200 to 1250°C -328° to 2500°F -200 to 1370°C
N t/c 32 to 2282°F 0 to 1250°C 32 to 2372°F 0 to 1300°C
PT2 t/c 32 to 2540°F 0 to 1393°C 32 to 2543°F 0 to 1395°C
R t/c 32 to 2642°F 0 to 1450°C 32 to 3200°F 0 to 1760°C
S t/c 32 to 2642°F 0 to 1450°C 32 to 3200°F 0 to 1760°C
T t/c -328 to 662°F -200 to 350°C -328 to 750°F -200 to 400°C
1.0 RTD (DIN) -328 to 1202°F -200 to 650°C -328 to 1472°F -200 to 800°C
0.1 RTD (JIS) -199.9 to 999.9°F -143 to 636°C -328 to 1166°F -200 to 630°C
• Tenth degree resolution selectable over sensor operating range within limits of
-199.9 to 999.9, except for thermocouple types B, R, and S