Watlow’s Series 147 is an open-board temperature limit
with a thermocouple or RTD sensor input.
The Series 147 is designed to meet the needs of a wide
range of temperature limit applications. Installation and
setup are simple and easy, using basic hand tools. Factory
selectable options include high or low limit with either
manual or automatic reset on power loss.
The Series 147 has an LED output status indication
and can be ordered with an integral or a fixed set point.
(1885)
Control Mode
High or low limit, factory selectable
Manual or automatic reset on power loss, factory selectable
Latching alarm with manual reset on overtemperature
Customer-supplied reset switch
Operator Interface
LED indication of output status
Dial scale calibrated to compensate for sensor
non-linearities
Integral set point
Dual temperature scale (°F and °C)
Fixed set point
Manufactured to specified value
Input
Thermocouple or platinum RTD available
Thermocouple with automatic cold junction compensation
Thermocouple may be isolated or grounded
Thermocouple and RTD break protection de-energizes output
2- or 3-wire RTD input, 100, 500, or 1000 @ 0°C calibrated for
0.003850/ °C curve, factory selectable
Output
Electromechanical relay, 8A, Form C, SPDT: 8A @ 240VÅ resistive,
8A @ 28VÎ (dc) resistive, 275VA pilot duty rated
Accuracy
Adjustable Set Point
Calibration accuracy: ±1% of span, at 77°F ±5°F (25°C ± 3°C)
ambient and rated line voltage ± 1%
Set point accuracy: ±3% of dial scale
Accuracy span: 1000°F (540°C) minimum
Fixed Set Point
Calibration accuracy: ±10°F/±6°C of setting, at 77°F ±5°F (25°C
±3°C) ambient and rated line voltage ±1%
Agency Approvals
CE: EN61010 - Safety
EN61326 - Industrial Immunity, Class B Emissions
Installation Category 2, Pollution Degree 2
873 Recognized, File #E43684
Recognized to C22.2 No. 24, File #E43684
Approved for use in commercial cooking applications
FM Class 3545
Terminals
Sensor input and remote setpot
Screw clamp terminal: 12-26 gauge wire
Power input and control output
#6 screws on barrier strip
Power
120V~, +10%/-15%, 50/60 Hz
230V~ to 240~, +10%/-15%, 50/60 Hz
10VA maximum power
Operating Environment
32 to 131°F (0 to 55°C)
0 to 90% RH, non-condensing
Storage temperature: -4 to 185°F (-20 to 85°C)
Dimensions
Width: 4.5 in (114 mm)
Length: 4.0 in (102 mm)
Depth: 1.5 in (38 mm)
Weight
0.7 lb (0.3kg)
UL
®
is a registered trademark of Underwriters Laboratories, Inc.
Note: Specifications subject to change without notice.
Specifications
General Description
$5.00 Made in the U.S.A.
Printed on Recycled Paper
10% Postconsumer Waste
0600-0004-0011 Rev E
August 2000
Supersedes: 0600-0004-0011 Rev D
TOTAL
3 Year Warranty
Seitenansicht 0
1 2 3 4 5 6

Inhaltsverzeichnis

Seite 1 - Series 147

Series 147User’s ManualTemperature LimitWatlow Controls1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580Phone: 507/454-5300, Fax:

Seite 2 - Troubleshooting

2 Watlow Series 147 User’s Manual(1886) 147 _ - _ _ _ _ - _ 0 0 0 Output TypeE = Electromechanical relay, 8A,Form CLine Voltage1 = 120V~2 = 230V~ to

Seite 3 - Installation

4 Watlow Series 147 User’s ManualUse the following procedure to mount and install theWatlow Series 147 temperature limit control.1. Locate and drill

Seite 4 - Declaration of Conformity

1 Watlow Series 147 User’s ManualDeclaration of ConformitySeries 147WATLOW WINONA1241 Bundy BoulevardWinona, Minnesota 55987 USADeclares that the f

Seite 5 - Input Wiring

5 Watlow Series 147 User’s ManualThermocoupleFigure 5a — Thermocouple wiring.2- and 3-wire RTDFigure 5b — 2- and 3-wire RTD wiring.NOTE: 2- or 3-wir

Seite 6 - System Example

6 Watlow Series 147 User’s ManualFigure 4 — System wiring examples.12348910111256713Series 965Temperature Controller93BB-1CA0-00RG 4 (+) 5 (-)120V~