1 Watlow Series 103 User’s Manual
(2001)
Control Mode
On-off
Nominal switching hysteresis, typically 3°F (1.7°C)
Operator Interface
LED indication of output status
Dial scale calibrated to compensate for sensor non-linearities
Integral set point
Dual temperature scale (°F and °C)
Fixed set point
Manufactured to specified value
Input
Thermocouple or platinum RTD available
Thermocouple with automatic cold junction compensation
Thermocouple may be isolated or grounded
Thermocouple and RTD break protection de-energizes output
2- or 3-wire RTD input, 100, 500 or 1000 @ 0°C calibrated
for 0.003850/ °C curve, factory selectable
Output
Solid-state relay, Form A, 0.5A @ 24V~ min., 264V~ maximum,
opto-isolated, zero cross switching
Switched dc signal provides a non-isolated minimum turn-on volt-
age of 3VÎ (dc) into a minimum 500 load, maximum on voltage
not greater than 32VÎ (dc)
Electromechanical relay, 8A, Form C, SPDT: 8A @ 240V~ resis-
tive, 8A, 28VÎ (dc) resistive, 275 VA pilot duty rated
Accuracy
Adjustable Set Point
Calibration accuracy: ±1% of span, at 77°F ±5°F (25°C ± 3°C)
ambient and rated line voltage ± 1%
Set point accuracy: ±3% of dial scale
Accuracy span: 1000°F (540°C) minimum
Fixed Set Point
Calibration accuracy: ±10°F/±6°C of setting, at 77°F ±5°F (25°C
±3°C) ambient and rated line voltage ±1%
Temperature Stability
Thermocouple: Typically 5µV/°F ambient (9µV/°C ambient) input
referenced
RTD: Typically 0.2°F/°F ambient (0.2°C/°C ambient)
Voltage Stability
±0.01% of span (min span of 1000°F or 540°C) per % of rated
line voltage
Agency Approvals
CE: EN61010 - Safety
EN61326 - Industrial Immunity, Class B Emissions
Installation Category 2, Pollution Degree 2
873, File #E43684
to C22.2 No. 24, File #E43684
Approved for use in commercial cooking applications
Terminals
Captive screw, cage clamp connection, 0.155 in. (4mm) max.
width screwdriver blade, 30 to 14-gauge wire
Mounting
DIN rail, DIN EN50022, 35mm x 7.5mm
Sub-panel mounting
Power
120V~, +10%/-15%, 50/60 Hz
230V~ to 240~, +10%/-15%, 50/60 Hz
10VA maximum power
Operating Environment
32 to 131°F (0 to 55°C)
0 to 90% RH, non-condensing
Storage temperature: -4 to 185°F (-20 to 85°C)
Dimensions
Width: 2.28 in (60 mm)
Height: 4.45 in (115mm)
Depth: 3.89 in (100 mm)
Weight
0.7 lb. (0.3kg)
UL
®
is a registered trademark of Underwriter’s Laboratories, Inc.
Note: Specifications subject to change without notice.
Specifications
Series 103
Users Manual
On/Off Temperature
Controller
1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507, Internet: http://www.watlow.com
TOTAL
3 Year Warranty
CUSTOMER
SATISFACTION
0600-0004-0007 Rev D
January 2001
Supersedes: 0600-0004-0007 Rev C
$5.00 Made in the U.S.A.
Printed on Recycled Paper
10% Postconsumer Waste
The Watlow Series 103 is a DIN rail mount, on-off
temperature controller with a thermocouple or RTD
sensor input. The DIN rail mounting offers quick and
easy installation with the use of simple hand tools.The
controller may also be flush mounted.
The Series 103 can be factory configured as either a
heat or cool output. Output types include electromechani-
cal relay, solid-state relay or open collector output.
The Series 103 has an LED for output status
indication and can be ordered with an integral, adjustable
set point or a fixed set point.
General Description
Seitenansicht 0
1 2 3 4 5 6

Inhaltsverzeichnis

Seite 1 - Series 103

1 Watlow Series 103 User’s Manual(2001)Control Mode• On-off• Nominal switching hysteresis, typically 3°F (1.7°C)Operator Interface• LED indication o

Seite 2 - Dimensions

Figure 2a — Series 103 dimensions.Sub-Panel Mounting the Series 1031.Using the controller as a location template, mark bothmounting holes.2.Drill two

Seite 3 - Power Wiring

ThermocoupleFigure 3b — Thermocouple wiring.2- and 3-wire RTDFigure 3c — 2- and 3-wire RTD wiring.NOTE: 2- or 3-wire RTD input, calibrated for 0.00385

Seite 4 - Trim 5/8”

4 Watlow Series 103 User’s ManualFigure 4 — System wiring examples.12348910111256713Series 103TemperatureController103C-1620-10004 (+)5 (-)120V~L1L2

Seite 5

5 Watlow Series 103 User’s ManualTrim 5/8”Declaration of ConformitySeries 103WATLOW WINONA1241 Bundy BoulevardWinona, Minnesota 55987 USADeclares t

Seite 6 - Troubleshooting

6 Watlow Series 103 User’s Manual(2002) 103 _ - _ _ _ _ - _ 0 0 0Output TypeC = Switched dc, non-isolatedE = Electromechanical relay, 8A,Form CK = S