Watlow EZ-ZONE PM Express Bedienungsanleitung Seite 15

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 35
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 14
EZ-ZONE PM Express (PID) 15 Install and Wire
Switched DC
Supplied current up to a maximum of 30 mA. See
Power Supply note above.
Short circuit limited to <50 mA
22 to 32VÎ (dc) open circuit voltage
Use dc- and dc+ to drive external solid-state relay.
DIN-A-MITE compatible
- single-pole: up to 4 in parallel or 4 in series
- 2-pole: up to 2 in parallel or 2 in series
- 3-pole: up to 2 in series
Open Collector
100 mA maximum output current sink
30VÎ (dc) maximum supply voltage
Any switched dc output can use the common
terminal.
Use an external power supply to control a dc load,
with the load positive to the positive of the power
supply, the load negative to the open collector and
common to the power supply negative.
See Quencharc note.
Mechanical Relay Form C
5 A at 240VÅ (ac) or 30VÎ (dc) maximum resis-
tive load
20 mA at 24V minimum load
125 VA pilot duty at 120/240VÅ (ac), 25 VA at
24VÅ (ac)
100,000 cycles at rated load
Output does not supply power.
For use with ac or dc
See Quencharc note.
Mechanical Relay Form A
5 A at 240VÅ (ac) or 30VÎ (dc) maximum resis-
tive load
20 mV at 24V minimum load
125 VA pilot duty @ 120/240VÅ (ac), 25 VA at
24VÅ (ac)
100,000 cycles at rated load
Output does not supply power.
For use with ac or dc
See Quencharc note.
NO-ARC Relay Form A
15 A at 85 to 264VÅ (ac) resistive load only
1/16 DIN models only
2,000,000 cycle rating for NO-ARC circuit
100 mA minimum load
2 mA maximum off state leakage
Do not use on dc loads.
Output does not supply power.
Solid-State Relay Form A
0.5 A at 20 to 264VÅ (ac) maximum resistive
load
20 VA 120/240VÅ (ac) pilot duty
Opto-isolated, without contact suppression
Maximum off state leakage of 105 microamperes
Output does not supply power
Do not use on dc loads.
See Quencharc note.
Universal Process
4 to 20 mA into 800 Ω maximum load
0 to 10VÎ (dc) into voltage 1 kΩ minimum load
Scalable
Output supplies power (See Power Supply note
previous page).
Cannot use voltage and current outputs at same
time
Quencharc Note:
Switching pilot duty inductive loads (relay coils, solenoids, etc.) with
the mechanical relay, solid state relay or open collector output op-
tions requires use of an R.C. suppressor.
L2
K2
Mechanical Relay Form A
PM _ C _ _ (J) - A A A A B _ _
Seitenansicht 14