Series 935B
Temperature Controller
with Countdown Timer
1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507, http://www.watlow.com
U.S. English
Now with Remote
Timer Start and
Fully DIN-a-mite
®
Compatible
User Levels:
New User ...................................... Go to page 2
Experienced User / Set-Up ........ Go to page 11
Expert User ................................ Go to page 51
Installers:
Mounting ..................................... Go to page 40
Wiring Information .......................Go to page 44
Seitenansicht 0
1 2 3 4 5 6 ... 59 60

Inhaltsverzeichnis

Seite 1 - Series 935B

0600-0015-0001 Rev C $15.00July 2000Supersedes: 0600-0015-0001 Rev BRegistered Company Winona, Minnesota USA ISO 9001TOTAL3 Year WarrantyCUSTOMERSATI

Seite 2 - Your Comments

Respond to a simple errorDisplay Probable Cause Recommended ActionReversed thermo- Change the sensorcouple connection leads on Terminals+ to –. 1 and

Seite 3 - Where to find it…

,,,Watlow Series 935B User’s Manual 11Software Organization• The Series 935B has three primary menus in addition to a normal display.• The software

Seite 4 - Introduction

12 Watlow Series 935B User’s ManualThe Series 935B Operations Menu is the first menu you encounter when you press the . and , keys simultane-ously for

Seite 5 - Dual Output

Watlow Series 935B User’s Manual 13Table 4 - Operations Menu Overview To enter the Operations Menu, press the . and , keys simultaneously for three

Seite 6 - Information is Easy

14 Watlow Series 935B User’s ManualChoosing a PID Setting StrategyYou may rely solely on the Auto-tune [`Aut] function (p. 34) and factory defaults to

Seite 7

Setting PID Menu Values• Proportional Band, Heat and Cool [Pb`h] and [Pb`c]: Select a value (degrees) to set up band on either side (±)of the Primary

Seite 8 - Begin Controlling

16 Watlow Series 935B User’s ManualTable 5 - PID Menu Overview Set-Up HeatProportional Band Heat - Select a heat proportional band value.[```0] [`999]

Seite 9 - Change Set Point

Watlow Series 935B User’s Manual 17Set-Up GeneralIntegral Function - Select an integral value.[`)00] [9(99]0.00 to 99.99 minutes/repeatDerivative Fu

Seite 10 - Respond to a simple error

18 Watlow Series 935B User’s ManualThe Configuration Menu is the second sub-menu in the Operations Menu. Use it to set Inputs, Ranges, Output Types,Al

Seite 11 - Learn Easy Software Map

Watlow Series 935B User’s Manual 19NOTE:Access to Configuration Menu varies with lockout function. See p. 21.Alarm Hysteresis - Choose alarm switchi

Seite 12 - Learn the Operations Menu

Safety Information in this ManualNote, caution and warning symbols appear throughout this book to draw your attention toimportant operational and safe

Seite 13

20 Watlow Series 935B User’s ManualKey Lockout InformationThe Series 935B offers three different security, or “lockout,” options. Set upone or all thr

Seite 14 - Learn the PID Menu

Watlow Series 935B User’s Manual 21View Process Yes Yes Yes Yes Yes Yes YesView Set Point Yes Yes Yes Yes Yes Yes YesChange Set Point No Yes No Yes

Seite 15 - Setting PID Menu Values

22 Watlow Series 935B User’s ManualSetting Inputs and OutputsKey Input/Output Set-up Information• All initial input and output set-up occurs in the Co

Seite 16 - Learn the PID Menu - Details

Watlow Series 935B User’s Manual 23Table 8 - Setting Inputs and OutputsNOTE:Access to Configuration Menu varies with lockout function. See p. 21.Inp

Seite 17 - Set-Up General

(Closed switch = Starts Timer)Figure 5 - Remote Timer Start WiringSee p. 45 for more wiring information.24 Watlow Series 935B User’s ManualTo Set Up R

Seite 18 - Learn the Configuration Menu

Watlow Series 935B User’s Manual 25–1+2COM3RTS4OT15OT2678Load 2Load 1(Closed switch = locked panel)To Set Up Front Panel Lock…1. Install an external

Seite 19

26 Watlow Series 935B User’s ManualConfiguration Menu[``In]Input Type[`C_F]Celsius/Fahrenheit[``rL]Input Range Low[``rh]Input Range High[`Ot1]Output 1

Seite 20 - Using Lockout Functions

Set PointDeviationnormallyclosedDeviationnormallyopenProcess normallyclosedProcessnormallyopen Non-Alarm StateLED offAlarm Output:Alarm StateLED onAla

Seite 21 - [`rts] [SLOC] [`tAG]

28 Watlow Series 935B User’s ManualTo Set Up Series 935B Alarms…1. Plan an alarm strategy. What do youwant to happen when an alarm occurs?2. Wire the

Seite 22 - Setting Inputs and Outputs

Watlow Series 935B User’s Manual 29SETLatching alarmSilence alarmWith this selection, an alarmcannot be silenced at the 935Bfront panel (unless the

Seite 23 - Configuration Menu

Watlow Series 935B User’s Manual 3Where to find it…Table of ContentsItem ... PageIntroduct

Seite 24

30 Watlow Series 935B User’s ManualConfiguration Menu[``In]Input Type [`C_F]Celsius/Fahrenheit[``rL]Input Range Low[``rH]Input Range High[`Ot1]Output

Seite 25 - Using Front Panel Lockout

Watlow Series 935B User’s Manual 31Table 12 - Series 935B Timer Functions/SettingsDelay ONDelay OFF Signal ON Signal OFFOutput 2 TimerOutput Functio

Seite 26 - Learning Alarms

32 Watlow Series 935B User’s Manual3015 450To Set Up the 935B Timer…1. Plan a timer strategy.2. Wire the Output 2 control output, associated switching

Seite 27 - [deno] [prnc]

Watlow Series 935B User’s Manual 333015 450Convection Oven ApplicationScenarioA master chef bakes bread at 350°F for 30 minutes. He wants the oven a

Seite 28 - Setting and Clearing Alarms

34 Watlow Series 935B User’s ManualAuto-tuningManual Tuning For optimum performance, tune the Series 935B to your thermal system. The settings here ar

Seite 29

Watlow Series 935B User’s Manual 35Tweaking PID Settings1. Set [Pb`h] and [Ct`h] in degrees.2. If Proportional Band Heat [Pb`h] = 0, Set Hysteresis

Seite 30 - Learn the Countdown Timer

36 Watlow Series 935B User’s ManualCalibrating the 935BQuick CalibrationRestore:Press all three keyssimultaneously until[tc50] appears in thedisplay,

Seite 31 - ß press will display

Watlow Series 935B User’s Manual 37Calibrating the 935BThermocouple Input Field Calibration ProcedureEquipment Required:• Type “J” Reference Compens

Seite 32 - Setting the Countdown Timer

38 Watlow Series 935B User’s ManualErrors and TroubleshootingKey Error InformationSet up an input failure operation mode at the [FAIL] prompt in the [

Seite 33 - Timer Example Application

Watlow Series 935B User’s Manual 39Table 13 - Possible Displayed Error Codes and ActionsTo Troubleshoot Sensor• Remove sensor wires from Terminals 1

Seite 34 - Auto-tuning

4 Watlow Series 935B User’s ManualWelcome to the Watlow Series 935B!General DescriptionThe Series 935B is a temperature controller with countdown time

Seite 35 - Tweaking PID Settings

40 Watlow Series 935B User’s Manual0.874"(22.2mm)+0.012",-0.000"(+0.3mm,-0.0mm)0.500"(12.7mm)0.500"(12.7mm)2.272"(57.7mm

Seite 36 - Calibrating the 935B

Watlow Series 935B User’s Manual 412.09" (53.1mm)1.14"(29.0mm)Panel Cutout1.770" (44.96mm)4.00" (101.6mm)0.50" (12.7mm)Maxi

Seite 37

42 Watlow Series 935B User’s ManualInstalling the Series 935BInstallation Procedure1. Make a panel cutout using the tear-out mounting template, or the

Seite 38 - [FAIL} [bPLS]

Watlow Series 935B User’s Manual 43Terminal Block RemovalFigure 14- Terminal Block Removal Procedure2. Move your grip rearward slightly,then lift th

Seite 39

44 Watlow Series 935B User’s ManualWiring a 935BFigure 15 - Wiring the Series 935BÓWARNING: All wiring and fusing must conform to local andnational el

Seite 40 - Mounting

Watlow Series 935B User’s Manual 45System Wiring ExamplesÓWARNING: All electrical wiring and fusing must conform to local and national electric code

Seite 41 - Dimensions

46 Watlow Series 935B User’s ManualGlossaryAlarmA condition, generated by the controller,indicating that the process has exceeded orfallen below the s

Seite 42 - Installing the Series 935B

Watlow Series 935B User’s Manual 47AAuto-tune [`Aut] . . . . . . . . . . . . . . 12, 34AlarmsAlarm High [`AhI] . . . . . . . . . . 12, 26Alarm Low

Seite 43 - Terminal Block Removal

48 Watlow Series 935B User’s ManualSpecifications• Height• Length• WidthSpecifications—(1951)Control Mode• Auto-tune PID.• PID, PD, PI, on/off.• Count

Seite 44 - Wiring a 935B

Ordering Information—(1952) 9 3 5 B - 1 C C 0 - _ _ 0 _Single thermocouple or RTD (DIN) input,dual output, single display temperaturecontrol with time

Seite 45 - System Wiring Examples

Watlow Series 935B User’s Manual 5Output 1Output 2RDY21SETSingleInputDual OutputSingle InputType J, K, T, N, S, E Thermocouple, 1° RTD, or 0.1° RTDO

Seite 46 - Process Alarm

50 Watlow Series 935B User’s ManualCE Compliant ProductDeclaration of ConformitySeries 935WATLOW CONTROLS1241 Bundy BoulevardWinona, Minnesota 55987

Seite 47

Watlow Series 935A User’s Manual 51935B Software MapOperations MenuPrompt Range Default Hidden if * Your Settings*NOTE:All prompts, except[``SP] and [

Seite 48 - Specifications

52 Watlow Series 935A User’s ManualOperations MenuPrompt Range Default Hidden if * Your Settings[`tA9] = [P```];or if [Pb`h] ≠ 03°F or 2°C[```1] [`999

Seite 49 - 9 3 5 B - 1 C C 0 - _ _ 0 _

[`tA9] = [P```];or if [Pb`c] ≠ 03°F or 2°C[```1] [`999][```1] [`555][``)1] [99(0][``)1] [55%0]Select a value in wholedegrees (1°F to 999°F or1°C to 55

Seite 50 - CE Compliant Product

[`tA9] = [P```]0°F or 0°C[-999] [9999][-9(9] [99(9]Select a value,adjustable between -999° and 9999°F or Cor -99.9° and 999.9°F orC to eliminate adiff

Seite 51 - 935B Software Map

Watlow Series 935A User’s Manual 55Configuration MenuPrompt Range Default Hidden if * Your Settings[`tA9] = [``C`]heat[hEAt] [COOL][ALM] [`rSP][`FPL]

Seite 52

[`tA9] = [``C`];or if[`Ot1] and/or [`Ot2] ≠ [ALM]3°F or 2°C[```1] [`999][```1] [`555][``)1] [99(0][``)1] [55%0]Select a value in wholedegrees (1°F to

Seite 53

Watlow Series 935A User’s Manual 57Configuration MenuPrompt Range Default Hidden if * Your Settings[`tA9] = [``C`];or if[`Ot2] ≠ [thM] or[tMS]0°F or 0

Seite 54 - [`tA9] = [P```];

58 Watlow Series 935A User’s ManualConfiguration MenuPrompt Range Default Hidden if * Your SettingsAlways appearsP[PCOA] [`COA][PCO`] [`CO`][PC`A] [`C

Seite 55

About Watlow WinonaWatlow Winona is a U.S. division of Watlow Electric Manufacturing Company, St. Louis,Missouri, a manufacturer of industrial electri

Seite 56

6 Watlow Series 935B User’s ManualPress & read or press & changeReading or ChangingInformation is EasyYou can simply:• Read the normally displ

Seite 57

How to Reach UsQuality andMission Statement:To position Watlow Winonaas the world’s best supplierof superior thermalsolutions, by exceeding theexpecta

Seite 58

RDY21SETSeven-segmentalphanumeric display:• Shows process value,set point information, time, or• Shows prompt name or value, depending on the key comb

Seite 59 - Warranty

Begin ControllingTo Begin Controlling:1. Apply power to the system.A properly-wired Series 935B will begin controlling the thermal system as soon as y

Seite 60 - How to Reach Us

Change Set PointRDY21SETTo Change the Set Point:Your Series 935B displays the actual process temperature when it comes from the factory. You canchange